ROM Relay Output Module for NCS, 8 channels, 2 A at 250 Vac contacts
The ROM is a relay output module of the NET Concentrator System (NCS). It provides eight normally closed SPST, 1 form A relay channels, rated 2 A at 250 Vac or 2 A at 30 Vdc. The DIN-style housing mounts on 35 mm Top Hat rail.
- Model
- ROM/IO/RNC8/IP [DIN]
- Type
- Relay output module for NCS
- Outputs
- 8 relay channels (normally closed)
- Relay
- SPST, 1 form A
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
ROM/IO/RNC8/IP [DIN] is the relay output module of the NET Concentrator System (NCS), which also includes the AIM, AOM, CPM, DIM, EMM and TIM modules. It turns commands from the host system into contact closures in field circuits.
There are eight relay output channels, normally closed. Each is an SPST relay, 1 form A. The contact rating is 2 A at 250 Vac, 50/60 Hz, non-inductive load, or 2 A at 30 Vdc. The output type is discrete (contact closure) and the network type is the NCS system. The module has no maths or logic capability.
The DIN-style housing mounts on 35 mm Top Hat rail. For hazardous areas the module is listed Non-Incendive/Div. 2, Zone 2. It is RoHS compliant.
DXF and DWG drawings and a 3D CAD model are offered for the module.
In the order code ROM/IO/RNC8/IP [DIN] the Input field is IO, the Output field is RNC8 and the Power field is IP. The RNC8 designation corresponds to eight normally closed relay channels, and the contacts are rated for 250 Vac or 30 Vdc at 2 A.
Technical specifications
| Model | ROM/IO/RNC8/IP [DIN] |
|---|---|
| Type | Relay output module for NCS |
| Outputs | 8 relay channels (normally closed) |
| Relay | SPST, 1 form A |
| Contact rating | 2 A at 250 Vac, 50/60 Hz, non-inductive; 2 A at 30 Vdc |
| Output type | Discrete, contact closure |
| Network type | NCS system |
| Math or logic | No |
| Housing | DIN-style, 35 mm Top Hat rail |
| Hazardous area certification | Non-Incendive/Div. 2, Zone 2 |
| RoHS | Yes |
Part numbers
Show all part numbers (1)
ROM/IO/RNC8/IP [DIN]
Request a price and lead time
ROM Relay Output Module for NCS, 8 channels, 2 A at 250 Vac contacts. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How many relay outputs does the ROM have, and of what type?
Eight outputs, each an SPST, 1 form A relay, normally closed.
What current and voltage can the contacts switch?
2 A at 250 Vac (50/60 Hz, non-inductive load) or 2 A at 30 Vdc.
What hazardous area certification is listed?
Non-Incendive/Div. 2, Zone 2.