
EZ-ZONE® RMZ EtherCAT temperature control module with fibre optic sensor inputs
High RF fields upset ordinary electrical sensor readings, which is where the optical input option on the EZ-ZONE® RMZ comes in. The module links an RM control stack to an EtherCAT master and handles from one to 34 control loops.
- Fieldbus
- EtherCAT, RJ-45
- Control loops
- 1 to 34 (installation guide shows RMZ4 up to 48)
- Fibre optic inputs
- 4 sensors (option)
- System modules
- loops, limits, digital and analogue I/O
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Equipment with strong RF fields is a hard place to measure temperature: electrical sensors pick up interference and readings drift. Fibre optic sensors are immune to that, and the RMZ can take four of them on an optional optical sensor card, bringing the measurement straight into the control system. Doing it this way saves panel space, shortens response time and removes a separate signal conditioner from the scheme.
Within the modular EZ-ZONE RM family the RMZ is the network head. Behind it sit control loop modules, temperature limits and digital and analogue I/O, and the RMZ presents all of them to an EtherCAT-based temperature or logic controller. Its object dictionary follows the ETG.5003 semiconductor device profile, module profile 2060 for a temperature controller, and flags optical sensor and limit sensor faults as separate status bits.
The product page quotes one to 34 control loops, whereas the installation guide shows an RMZ4 arrangement with up to 48 loops, so the loop count should be checked against the exact build. Other versions add a serial communications card with Bluetooth, or DeviceNet on an M12 connector alongside Modbus for an operator panel. EtherCAT uses RJ-45, Modbus RTU RS-485 uses RJ-12, and a USB port is provided.
Where the plant network is not EtherCAT, the same optical technology is available in the EZ-ZONE RMF, which accepts up to eight sensors and talks other industrial protocols. An ESI file, the object dictionary and 3D STEP models support integration.
Technical specifications
| Fieldbus | EtherCAT, RJ-45 |
|---|---|
| Control loops | 1 to 34 (installation guide shows RMZ4 up to 48) |
| Fibre optic inputs | 4 sensors (option) |
| System modules | loops, limits, digital and analogue I/O |
| Additional interfaces | DeviceNet on M12, Modbus RTU RS-485 on RJ-12, USB, Bluetooth |
| Device profile | ETG.5003, module 2060 |
| Diagnostics | optical sensor fault, limit sensor fault |
| Non-EtherCAT version | EZ-ZONE RMF, up to 8 sensors |
Request a price and lead time
EZ-ZONE® RMZ EtherCAT temperature control module with fibre optic sensor inputs. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How many fibre optic sensors does the RMZ accept?
Four, on the optional optical sensor card. The RMF module without EtherCAT takes up to eight.
Which network connects it to the PLC?
EtherCAT over RJ-45 using the ETG.5003 profile; versions with DeviceNet on M12 and Modbus RTU RS-485 also exist.
Why use optical temperature sensing?
Optical sensors do not pick up RF interference, so readings stay accurate in equipment with strong high-frequency fields.
Similar equipment from other manufacturers






