Series 12400 digital displacer level and interface transmitter/controller, SIL 2 capable, ATEX
A digital head for torque-tube displacer level measurement, used as a transmitter or as a controller on liquid level and liquid-liquid interface duties. Typical homes are refinery and petrochemical vessels in hazardous areas where a SIL 2 rated instrument is required.
- Type
- digital displacer level transmitter/controller
- Measurement
- liquid level, liquid-liquid interface
- Sensing element
- displacer on torque tube
- Functional safety
- up to SIL 2 at HFT=0, IEC 61508 / IEC 61511
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Safety integrity is what most buyers look at first with this series. Following the renewed certification, the transmitter is SIL capable up to SIL 2 at HFT=0 under IEC 61508 and IEC 61511, and that holds even when the SIL 2 device feature is switched off. The feature itself is enabled or disabled through a DTM and the manufacturer's configuration software.
Mechanically the instrument follows the classic displacer principle. A displacer hangs in a cage or directly in the vessel, the torque tube converts its buoyancy change into rotation, and the digital head turns that into the output signal or, on controller versions, into the control action. It handles a single liquid level or the interface between two immiscible liquids on separators, columns, drums and storage vessels. One point to note on retrofits: a head built to the SIL design carries a bias block and cannot be fitted to 12120 or 12800 torque tubes.
For hazardous areas there are two ATEX routes, intrinsic safety and flameproof. A dedicated ATEX manual sets out the markings, allowable supply voltage, maximum power, electrical connections and conduit entries for each. The series also holds Kazakhstan metrology pattern approval.
The numbering system defines cage mounting, connection type and whether the unit is a transmitter or a controller. Error and warning messages are tabulated together with the device action, so the operator can see whether the instrument simply warns or drives its output to the failsafe position.
Technical specifications
| Type | digital displacer level transmitter/controller |
|---|---|
| Measurement | liquid level, liquid-liquid interface |
| Sensing element | displacer on torque tube |
| Functional safety | up to SIL 2 at HFT=0, IEC 61508 / IEC 61511 |
| Hazardous area | ATEX intrinsic safety, flameproof |
| SIL configuration | via DTM and manufacturer's software |
| SIL head compatibility | not for 12120/12800 torque tubes |
| Approvals | Kazakhstan metrology pattern approval |
| Versions | transmitter or controller |
Request a price and lead time
Series 12400 digital displacer level and interface transmitter/controller, SIL 2 capable, ATEX. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Can the 12400 be used in a safety instrumented function?
Yes, it is SIL capable up to SIL 2 at HFT=0 to IEC 61508 and IEC 61511. The SIL 2 feature is switched on through the DTM.
Will the digital head fit an older pneumatic displacer?
A SIL design head has a bias block and cannot go on 12120 or 12800 torque tubes. Other combinations are checked against the order code.
Which hazardous area protection is available?
ATEX intrinsic safety and ATEX flameproof versions are offered. Markings and supply limits are given in the ATEX manual.