EPack SCR-1PH, -2PH and -3PH compact thyristor power controllers, up to 125 A and 500 V
Compact SCR power controllers for electric heating loads, offered in single-phase, two-leg and three-leg versions. Measurement, load diagnostics and Ethernet are built in, and the units mount on DIN rail or a panel.
- Type
- SCR (thyristor) power controller
- Versions
- 1PH, 2PH (two-leg control), 3PH (three-leg control)
- Nominal load current
- up to 125 A
- Operating voltage
- 100–500 V
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Choice of version comes down to the load. The 3PH model controls every phase on its own, so it holds accurate control even when the three phases are unbalanced, and its current and voltage readings feed alarms as well as monitoring of impedance, energy and reactive power. The 2PH model handles a three-phase load through two legs, which suits balanced loads connected directly or via a transformer; burst firing avoids harmonics and cuts reactive power draw. The 1PH model covers single-phase circuits.
Ratings reach 125 A nominal load current, with an operating voltage of 100 V to 500 V that can be set within the same variant. In heating terms that is 400 W to 62.5 kW for 1PH and up to 108 kW for 3PH. Suitable loads include resistive and infrared heaters, transformer primaries and silicon carbide elements, under V², I² or true power control.
Set-up is done from the front panel or from PC software, and a finished configuration can be copied to further units. Each controller measures current, voltage, power, impedance and energy, and reports load faults through an alarm relay, the display or the network. Communications use Modbus TCP together with EtherNet/IP or PROFINET, and a built-in dual-port Ethernet switch allows daisy-chain wiring. Zero-configuration networking removes manual address set-up, and OEM security protects the stored settings.
The housing is fanless and rated IP20. Compliance covers IEC/EN 60947-4-3:2014 and UL60947-4-1, with a short-circuit current rating of 100 kA when fitted with high-speed fuses. Install in a non-corrosive, non-explosive and non-conductive atmosphere.
Technical specifications
| Type | SCR (thyristor) power controller |
|---|---|
| Versions | 1PH, 2PH (two-leg control), 3PH (three-leg control) |
| Nominal load current | up to 125 A |
| Operating voltage | 100–500 V |
| Heating power | 400 W to 62.5 kW (1PH), up to 108 kW (3PH) |
| Control modes | V², I², true power |
| Loads | resistive, infrared, transformer primary, silicon carbide |
| Communications | Modbus TCP, EtherNet/IP or PROFINET, built-in 2-port Ethernet switch |
| SCCR | 100 kA with fuse |
| Mounting | DIN rail or panel, fanless |
| Standards | IEC/EN 60947-4-3:2014, UL60947-4-1 |
| Protection | IP20 |
Request a price and lead time
EPack SCR-1PH, -2PH and -3PH compact thyristor power controllers, up to 125 A and 500 V. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
When should the 2PH version be chosen over the 3PH?
The 2PH suits balanced three-phase loads, including those fed through a transformer; for unbalanced loads the 3PH controls each phase separately.
Which fieldbus protocols are supported?
Modbus TCP plus EtherNet/IP or PROFINET, through a built-in dual-port Ethernet switch for daisy chaining.
What short-circuit rating does the controller carry?
It has been tested to an SCCR of 100 kA with high-speed fuses.