DPS 1200 DIN-style 1200 mA switching power supply, 24 V DC
The DPS 1200 is a stand-alone switching power supply for DIN rail, giving 24 V DC at up to 1200 mA. It takes 90 to 260 V AC, protects its output against overvoltage and short circuits and isolates input from output.
- Model
- DPS 1200
- Type
- DIN-style switching power supply
- Output
- 24 V DC, adjustable ±10%
- Output current
- 1200 mA maximum at 50 °C
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The DPS 1200 is a stand-alone switching power supply that produces 24 V DC at a maximum rated output of 1200 mA. The output can be adjusted to at least 24 V DC ±10%. The housing is DIN-rail style, and the rail can go on a wall, in a rack or in a NEMA enclosure.
The output is continuously protected against overvoltage and short circuits. When either condition is detected the supply shuts down and tries to recover by raising the output voltage, and full recovery occurs once the fault is removed. Input and output are isolated, cooling is by convection and the circuit is derated for added dependability.
Nine removable terminal blocks are supplied, one three-position block for input power and eight two-position blocks for the 24 V DC output. Removable blocks let individual loops be isolated for troubleshooting, maintenance and calibration without disturbing field wiring. A constant red LED shows normal operation.
Figures are load regulation of 1% maximum for a ±40% change from 60% of rated load, hold-up time of 20 ms minimum, ripple of 100 mV maximum at 100 kHz and 200 mV maximum at 10 MHz, typical efficiency of 70%, and 1100 V AC isolation between case, input and output. The switching frequency is above 20 kHz and the input frequency is 47 to 450 Hz. The operating ambient is 0 °C to +50 °C with an effect of ±0.05% maximum per °C, and the weight is 1.14 kg.
The order code is DPS / 24DC / 1200MA / 90-260AC [DIN], with 1200 mA available at up to 50 °C. A single internal potentiometer (VR1) sets the output voltage.
Technical specifications
| Model | DPS 1200 |
|---|---|
| Type | DIN-style switching power supply |
| Output | 24 V DC, adjustable ±10% |
| Output current | 1200 mA maximum at 50 °C |
| Input voltage | 90 to 260 V AC |
| Input frequency | 47 to 450 Hz |
| Housing | DIN rail style |
| Terminal blocks | Removable: one three-position input and eight two-position output, nine in total |
| Protection | Output overvoltage; short circuit |
| Efficiency | 70% typical |
| Isolation | 1100 V AC between case, input and output |
| Ripple | 100 mV (100 kHz); 200 mV (10 MHz) |
| Ambient range | 0 °C to +50 °C |
| Weight | 1.14 kg |
Part numbers
Show all part numbers (2)
DPS1200, code DPS / 24DC / 1200MA / 90-260AC [DIN]
How it compares with similar models
| Parameter | DPS 1200 DIN-style 1200 mA switching power supply, 24 V DC | DPS 240 DIN-style 240 mA instrument power supply, 24 or 42 V DC | SMP surface-mount linear DC instrument power supply | ECA DIN rail current and voltage limit alarm trip, two relays, 24DC supply |
|---|---|---|---|---|
| Type | DIN-style switching power supply | DIN-style power supply | Linear regulated DC power supply | current and voltage limit alarm trip |
| Input voltage | 90 to 260 V AC | 117, 220 or 240 V AC, 50/60 Hz | 100, 117, 220, 230, 240 V AC; 47 to 440 Hz | — |
| Housing | DIN rail style | Aluminium, DIN style, for G-rail | Aluminium, ventilated | aluminium, G-type and Top Hat DIN rail |
| Protection | Output overvoltage; short circuit | Short circuit; short-term overload | Short circuit and overload, automatic limiting | — |
| Isolation | 1100 V AC between case, input and output | 1100 V RMS between case, input and output | — | 1500Vrms between input, output and power |
| Ambient range | 0 °C to +50 °C | 0 °C to +70 °C | 0 °C to +50 °C | — |
Request a price and lead time
DPS 1200 DIN-style 1200 mA switching power supply, 24 V DC. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What happens at a short circuit on the output?
The supply shuts down and tries to recover, with full recovery once the fault is removed.
What input voltage does it accept?
90 to 260 V AC at 47 to 450 Hz.
How many terminal blocks are there?
Nine removable ones: one three-position input block and eight two-position output blocks.