DIN-A-MITE D SCR power controller, up to 100 A at 600 V, mercury relay replacement

A single-phase SCR controller for electric heat rated up to 100 A at 600 V AC. Its back-panel footprint matches a standard 100 A mercury displacement relay, so it drops into existing panels without new drilling.

Current
up to 100 A at 600 V AC and 30 °C; 80 A at 50 °C
Phases
1 (3-phase with two or three units)
Switching
zero-cross
Command input
variable time base, 4–20 mA, VAC/VDC

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Fuses come built in. Semiconductor fuses sit on the board and are reached from the front, so no separate fuse holder has to be mounted. With the specified fuses the unit carries a 200 kA short-circuit current rating, tested up to 480 V. The whole assembly is touch-safe.

Current rating is 100 A single-phase at 600 V AC with a 30 °C ambient, falling to 80 A at 50 °C into a resistive load. Three-phase heaters are handled by using two or three controllers together. Permitted ambient range is 0–85 °C, and switching is zero-cross through back-to-back SCRs.

Many heating panels still carry mercury displacement relays, and the D model is aimed squarely at them: same 100 A footprint, no mercury. Command inputs are ordered as variable time base, 4–20 mA or a VAC/VDC contactor input. An optional on-board current transformer provides roughly 0.2 V AC per ampere for external load-current monitoring, and some models add a shorted-SCR alarm. All options are set by the model number.

Approvals cover UL 508 listing, C-UL, CE with filter and RoHS 2, which helps panel builders whose assemblies must carry agency marks.

Technical specifications

Currentup to 100 A at 600 V AC and 30 °C; 80 A at 50 °C
Phases1 (3-phase with two or three units)
Switchingzero-cross
Command inputvariable time base, 4–20 mA, VAC/VDC
Fusessemiconductor, on board, front access
SCCR200 kA to 480 V
Current transformeroption, 0.2 V AC per amp
Mountingback panel, 100 A mercury relay footprint
Ambient temperature0–85 °C
ApprovalsUL 508, C-UL, CE, RoHS 2

Request a price and lead time

DIN-A-MITE D SCR power controller, up to 100 A at 600 V, mercury relay replacement. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Will DIN-A-MITE D fit where a mercury relay was?

Yes, its back-panel footprint matches a standard 100 A mercury displacement relay, so no new holes are needed.

How is a three-phase heater controlled?

The unit is single-phase, so two or three controllers are used together on a three-phase load.

What current is allowed in a warm cabinet?

Up to 100 A at 30 °C ambient and up to 80 A at 50 °C into a resistive load.