DIN-A-MITE B solid-state heater power controller, up to 40 A at 600 V, single or three phase
A small zero-cross SCR controller for switching resistive heater loads, with heat sink and terminations already sized for the job. It handles up to 40 A single-phase or 22 A three-phase at 600 V AC and contains no mercury.
- Current, single phase
- up to 40 A at 600 V AC
- Current, 3-phase 2-leg / 3-leg
- 33 A / 22 A
- Line voltage
- 24–48, 120–240, 277–600 V AC
- Switching
- zero-cross
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Ratings depend on wiring. At 600 V AC the unit switches up to 40 A on a single-phase load, 33 A on a two-leg three-phase arrangement and 22 A where all three legs are controlled, following the derating curve. Line-voltage versions cover 24–48 V, 120–240 V and 277–600 V. Surge withstand is 380 A for 16.6 ms, fuse selection should use an I²t of 4000 A²s, and dissipation runs at 1.2 W per amp switched.
Switching is zero-cross. Three command options are built to order: variable time base, 4–20 mA process signal, or a VAC/VDC contactor input. A shorted-SCR alarm can be added, and every option is fixed by the model number at the factory.
On the fault side, the controller carries a 200 kA short-circuit current rating, tested up to 480 V with the specified semiconductor fuses, which limits damage if a short occurs. Terminals are touch-safe and accept 0.2–1.5 mm² conductors tightened to no more than 0.5 Nm. DIN-rail and back-panel fixing both come as standard.
Panel builders use it in place of mercury or electromechanical contactors on equipment heated by resistive elements. Approvals comprise UL 508 listing, C-UL, CE with filter and RoHS, with EMC to EN 61326 and safety to EN 50178, installation category III and pollution degree 2. Ambient operating limit is 80 °C.
Technical specifications
| Current, single phase | up to 40 A at 600 V AC |
|---|---|
| Current, 3-phase 2-leg / 3-leg | 33 A / 22 A |
| Line voltage | 24–48, 120–240, 277–600 V AC |
| Switching | zero-cross |
| Command input | variable time base, 4–20 mA, VAC/VDC |
| Surge current | 380 A, 16.6 ms |
| I²t for fusing | 4000 A²s |
| Power dissipation | 1.2 W/A |
| SCCR | 200 kA to 480 V with fuses |
| Mounting | DIN rail or back panel |
| Terminals | 0.2–1.5 mm², up to 0.5 Nm |
| Ambient temperature | up to 80 °C |
| Approvals | UL 508, C-UL, CE, RoHS |
Request a price and lead time
DIN-A-MITE B solid-state heater power controller, up to 40 A at 600 V, single or three phase. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What current can DIN-A-MITE B switch on three phases?
Up to 33 A with two legs controlled and 22 A with three legs, at 600 V AC; single-phase rating is 40 A.
Which command signals can it accept?
Variable time base, 4–20 mA or a VAC/VDC contactor input, chosen through the model number.
Is it suitable for panels needing an SCCR rating?
Yes, with the recommended semiconductor fuses it carries a 200 kA short-circuit current rating, tested up to 480 V.