DIN-A-MITE® A solid-state power controller, single phase, up to 25 A at 600 V AC
A compact solid-state controller that switches a single-phase heating load of up to 25 A at 600 V AC, firing at zero cross. Heat sink and terminations are built in, so it clips onto DIN rail or screws to a back panel with no thermal design work.
- Type
- solid-state power controller
- Phases
- 1
- Maximum current
- 25 A
- Voltage
- up to 600 V AC
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Choosing a heat sink and suitably rated terminals is usually the fiddly part of fitting a thyristor switch. On the DIN-A-MITE® A both are integrated into the housing, which mounts on DIN rail or a back panel as standard. Output reaches 25 A, derated with ambient temperature according to the published curve, and the device is specified for ambients up to 80 °C (176 °F). It contains no mercury.
Switching is single-phase zero cross. Several input versions exist, all fixed at the factory by model number: variable time base, which follows a temperature controller and holds the process set point in ovens and furnaces without overshoot or droop; 4–20 mA process control from an analogue signal; and a contactor version driven by an AC or DC voltage input. TRU-TUNE®+ adaptive control and profiling are not offered on this model.
With the specified fusing, the controller carries a 200 kA short-circuit current rating, tested at up to 480 V AC, which helps protect against arc flash in the panel. Agency approvals are UL® 508, C-UL® and CE. DIN rail semiconductor fuses matched to the model number are recommended for protection.
Typical loads are resistance heaters in ovens, furnaces and similar electrical heating plant, especially where mechanical contactors wear out quickly under frequent cycling.
Technical specifications
| Type | solid-state power controller |
|---|---|
| Phases | 1 |
| Maximum current | 25 A |
| Voltage | up to 600 V AC |
| Output firing | zero cross |
| Control input | variable time base, 4–20 mA or AC/DC contactor input |
| SCCR | 200 kA, tested to 480 V AC with fusing |
| Approvals | UL® 508, C-UL®, CE |
| Ambient temperature | up to 80 °C (176 °F) |
| Mounting | DIN rail or back panel |
| TRU-TUNE®+ / profiling | not available |
Request a price and lead time
DIN-A-MITE® A solid-state power controller, single phase, up to 25 A at 600 V AC. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What current can the DIN-A-MITE® A switch?
Up to 25 A on a single phase at up to 600 V AC, with the usable current read from the derating curve for the actual ambient temperature.
Which control inputs are available?
Variable time base, 4–20 mA analogue and an AC or DC voltage contactor input, each selected by model number at the factory.
What short-circuit rating does it carry?
It has a 200 kA SCCR, tested at up to 480 V AC, provided the required fuses are fitted.