Series 5B Valve Status Monitor, Die Cast Aluminium Switch Box, up to 6 Switches, IP66/67
The Series 5B is a compact switch box for quarter-turn actuators, with a high contrast position indicator dome. It has a die cast aluminium body rated IP66/67 and NEMA 4 and 4X, takes up to six mechanical or proximity switches and offers up to 20 terminals, and can be specified SIL 3 capable.
- Type
- Switch box for quarter-turn actuators
- Body
- Die cast aluminium, grey polyester coating
- Indicator dome
- Polycarbonate
- Seal
- EPDM
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The 5B mounts on quarter-turn actuators of ball and butterfly valves and gives visual and electrical signals for open and closed positions. It fits the VDI/VDE 3845 (NAMUR) pattern, with brackets for mounting pads of 30 x 80 and 30 x 130 mm. Typical sectors include oil and gas, chemical and petrochemical plants, water and wastewater, pharmaceuticals, industrial gases, marine and shipbuilding, mining, power, pulp and paper, and sugar production.
The body and cover are die cast aluminium with a grey polyester coating, and the cover seal is an EPDM ring. The cover is held by captive stainless steel bolts placed outside the sealing zone, and non metallic washers under the bolts protect the coating during tightening. The polycarbonate indicator dome resists impact and can be turned through 90° to reverse the indication without removing the cover. The indicator shaft has a second seal that separates the indicator zone from the internal volume. Indicator colours are red and yellow as standard, red and green, or black and yellow.
Up to six switches fit inside. Mechanical options are SPDT rated 10 A at 250 V AC, low power SPDT, DPDT and reed switches. Proximity options are three wire PNP and NPN types, normally open or closed, working at 10 to 30 V DC, two wire types rated 20 to 140 V AC and 20 to 250 V AC, and intrinsically safe NAMUR sensors. Cams are slotted and the switching point is set without tools. The terminal block carries 12 or 20 poles and is angled towards the installer.
Instead of discrete signals the box can transmit switch status over AS-i, Profibus DP or DeviceNet. Two cable entries are provided, either 3/4 NPT or M25. With two SPDT switches fitted, the unit weighs about 1.1 kg.
The operating range is -25 to 65 °C. The enclosure is certified to NEMA 4, 4X and IP66/67, and has passed salt spray testing to UL 50E. Standard versions carry CE and cULus marks. The intrinsically safe version with NAMUR sensors is marked Ex ia IIC T6 under ATEX and IECEx, with ambient temperatures of -25 to 65 °C in Zone 1 and up to 49 °C in Zone 0.
Technical specifications
| Type | Switch box for quarter-turn actuators |
|---|---|
| Body | Die cast aluminium, grey polyester coating |
| Indicator dome | Polycarbonate |
| Seal | EPDM |
| Enclosure rating | IP66/67, NEMA 4, 4X, UL 50E salt spray |
| Number of switches | Up to 6 |
| Mechanical switches | SPDT, low power SPDT, DPDT, reed switch |
| Proximity switches | PNP, NPN (10–30 V DC), two-wire 140 V and 250 V, NAMUR |
| Terminals | 12 or 20 poles |
| Networks | AS-i, Profibus DP, DeviceNet |
| Cable entries | 2 x 3/4 NPT or 2 x M25 |
| Mounting | VDI/VDE 3845 (NAMUR) |
| Ambient temperature | -25 to 65 °C |
| Certifications | CE, cULus, SIL 3 capable; ATEX and IECEx optional |
| Weight with 2 x SPDT | 1.1 kg |
Part numbers
Show all part numbers (6)
5B0000-22600534, 5B0000-22630534, 5B0000-22650534, 5B0000-22601534, 5B0000-22631534, 5B0000-22651534
Request a price and lead time
Series 5B Valve Status Monitor, Die Cast Aluminium Switch Box, up to 6 Switches, IP66/67. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How can the open and closed indication be reversed without opening the box?
The indicator dome is turned through 90°. The cover does not need to come off, so the wiring stays enclosed.
Is a version for hazardous areas available?
Yes, with intrinsically safe NAMUR sensors marked Ex ia IIC T6 under ATEX and IECEx. The ambient range for Zone 1 is -25 to 65 °C.
Which network protocols does the box support?
AS-i, Profibus DP and DeviceNet. For the last two, GSD and EDS description files are available.