Series 54 inductive position sensor for quarter-turn valves, VDI/VDE 3845 mount

The compact series 54 inductive sensor shows the open and closed positions of quarter-turn valves and shut-off gates. It mounts directly on the actuator through a VDI/VDE 3845 interface, and PNP, AC/DC, AS-i or NAMUR outputs connect to any standard process control system.

Type
inductive position sensor, 2 sensors
Outputs
PNP, AC/DC, AS-i, NAMUR IS, 2-wire DC
Supply voltage
10–30 V DC (3-wire); 5–30 V DC (2-wire); 20–253 V AC (AC/DC); 26.5–31.9 V (AS-i); 8 V (NAMUR)
Switching frequency
PNP 0–500 Hz; AC/DC 25 Hz; AS-i 0–100 Hz; NAMUR 0–3 kHz

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The series 54 sensor is fitted to quarter-turn valve actuators to report the end positions of the gate or valve to the control system. The series is aimed at chemicals and petrochemicals, food and beverage, HVAC, industrial gases, marine and shipbuilding, mining, oil and gas, pharmaceuticals, power generation, pulp and paper, semiconductors, sugar and ethanol production, and water and wastewater treatment.

Inside the housing are two independent inductive sensors. They respond to two stainless steel targets on an actuating element that turns with the stem, so there are no contacts to wear, weld or spark. The actuating element is made from a low-resistivity material, does not build up static charge and works in either direction of rotation. A yellow indicator on the actuating element can be seen from a distance, and LEDs show power, switching state and solenoid status.

The housing is sealed and resists impact, vibration, ultraviolet light and corrosion. It withstands high pressure washdown and alkaline cleaning solutions, suits contaminated media and handles frequent switching cycles. No maintenance is needed in service.

The range has several variants. General Service has an extremely low profile with a PBT thermoplastic body, and its outputs are 2-wire DC or 3-wire PNP. Industrial Service, designated 54-IS, offers PNP, AS-i and AC/DC outputs plus one solenoid output. An intrinsically safe version has a NAMUR output and a temperature range from -25 to 100 °C. The 54-HS suits hazardous locations with a powder-coated aluminium and polycarbonate body, rated IP66/67/69K and -40 to 75 °C.

The nominal operating distance is 3 mm, with assured switching within 0 to 2.4 mm. Supply is 10 to 30 V DC for 3-wire, 5 to 30 V DC for 2-wire, 20 to 253 V AC for AC/DC, and 26.5 to 31.9 V from the AS-i bus. The AS-i version works as an A/B slave to specification V3.0. The intrinsically safe version is marked Ex ia IIC T6…T1 Ga to ATEX and IECEx and holds FM approval, while general models carry cULus, UL, CSA and CE.

Mounting dimensions are 30 x 80 mm or 30 x 130 mm, with connection by an M12 x 1 connector or an M20 x 1.5 cable gland. An optional Y connector combines power and signal from the sensor and the solenoid into one cable and cuts installation time.

Technical specifications

Typeinductive position sensor, 2 sensors
OutputsPNP, AC/DC, AS-i, NAMUR IS, 2-wire DC
Supply voltage10–30 V DC (3-wire); 5–30 V DC (2-wire); 20–253 V AC (AC/DC); 26.5–31.9 V (AS-i); 8 V (NAMUR)
Switching frequencyPNP 0–500 Hz; AC/DC 25 Hz; AS-i 0–100 Hz; NAMUR 0–3 kHz
Rated operating distance sn3 mm
Assured operating distance sa0–2.4 mm
Protection ratingIP66/67; IP66/67/69K
Temperature range-25 to 70 °C; -25 to 100 °C; -40 to 75 °C
Housing materialthermoplastic PBT; powder-coated aluminium and polycarbonate
MountingVDI/VDE 3845, 30 x 80 mm or 30 x 130 mm
ConnectionM12 x 1 connector; M20 x 1.5 cable gland
Explosion protectionEx ia IIC T6…T1 Ga (ATEX, IECEx)
CertificationscULus, UL, CSA, CE, ATEX, IECEx, FM

Part numbers

Show all part numbers (14)

540001-71104533, 540003-71104533, 540004-71104533, 540005-71104533, 540011-71104533, 540013-71104533, 540015-71104533, 540021-71104533, 540022-71104533, 540032-71104533, 540041-71104533, 540043-71104533, 541003-71104533, 541102-71104533

Request a price and lead time

Series 54 inductive position sensor for quarter-turn valves, VDI/VDE 3845 mount. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Does the series 54 work on an AS-Interface bus?

Yes. The AS-i version works as an A/B slave to specification V3.0 and needs a master at version V2.1 or later. It draws 26.5 to 31.9 V from the bus.

Which version suits a hazardous area?

The intrinsically safe version has a NAMUR output and the marking Ex ia IIC T6…T1 Ga. For non-sparking uses there is the 54-HS, with a powder-coated aluminium and polycarbonate housing rated IP66/67/69K.

How is the sensor fitted to the actuator?

The housing mounts directly on the actuator through a VDI/VDE 3845 interface, in footprints of 30 x 80 mm or 30 x 130 mm. The two-target actuating element is fitted to the stem.