Series 54-HS Inductive Valve Position Sensor for Hazardous Areas, NAMUR or DC 2-Wire
The Series 54-HS detects the open and closed positions of quarter-turn valves in hazardous areas without contact. It is supplied as an intrinsically safe NAMUR version or as a DC two-wire version rated IP66/67/69K.
- Type
- Inductive position sensor, 2 sensors
- Output
- NAMUR (intrinsically safe); DC two-wire, 2 x NO
- Supply voltage
- NAMUR 8 V; DC two-wire 6 - 30 V
- Rated operating distance
- NAMUR 0…2.4 mm; DC 0…2.05 mm
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The 54-HS is designed for process plants where quarter-turn valves must report their open and closed positions from inside a hazardous area. It copes with high pressure washdowns, caustic cleaning solutions, dirty process lines and frequent cycling, so it is often chosen where mechanical limit switches would soon wear out.
Inside the housing sit two independent inductive sensors, one for each end of travel. Because nothing touches the target, there is no contact wear, no welding of contacts and no arcing or sparking. The body is hermetically sealed against liquids and solids, and it resists shock, vibration, ultraviolet light and corrosion. LEDs show sensor power, switching state and solenoid status, and the unit needs no maintenance.
The intrinsically safe variant follows the NAMUR convention and runs from an 8 V intrinsically safe circuit. It senses from 0 to 2.4 mm, switches up to 3 kHz, carries an IP67 rating and works between -25 and 100°C. It holds a cULus Listed, General Purpose approval under file E248934. The DC two-wire variant runs from 6 to 30 V, senses from 0 to 2.05 mm, switches up to 100 Hz, carries IP66/67/69K and tolerates temperatures from -40 to 75°C.
Mounting follows the VDI/VDE 3845 pattern, so the sensor fits straight onto a compliant actuator and keeps the actuator profile small. The intrinsically safe version connects through a single M12 x 1 plug, a pair of M12 x 1 and RD24x18 plugs, or two M20 x 1.5 cable glands. Switching points are set with the activator fitted to the valve stem.
Technical specifications
| Type | Inductive position sensor, 2 sensors |
|---|---|
| Output | NAMUR (intrinsically safe); DC two-wire, 2 x NO |
| Supply voltage | NAMUR 8 V; DC two-wire 6 - 30 V |
| Rated operating distance | NAMUR 0…2.4 mm; DC 0…2.05 mm |
| Switching frequency | NAMUR 0…3 kHz; DC 0…100 Hz |
| Enclosure rating | NAMUR IP67; DC IP66/67/69K |
| Temperature range | NAMUR -25…100°C; DC -40…75°C |
| Mounting | NAMUR / VDI/VDE 3845 |
| Connection (NAMUR) | M12 x 1; M12 x 1 and RD24x18; two M20 x 1.5 cable glands |
| Certifications | cULus Listed, General Purpose (E248934) |
Request a price and lead time
Series 54-HS Inductive Valve Position Sensor for Hazardous Areas, NAMUR or DC 2-Wire. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How do the NAMUR and DC two-wire versions differ?
The NAMUR version runs from an 8 V circuit, switches up to 3 kHz and carries IP67. The DC two-wire version runs from 6 to 30 V, switches up to 100 Hz and carries IP66/67/69K.
Which version copes with the lowest temperatures?
The DC two-wire version operates from -40 to 75°C. The intrinsically safe NAMUR version operates from -25 to 100°C.
How is the intrinsically safe sensor connected?
You can use a single M12 x 1 plug, a pair of M12 x 1 and RD24x18 plugs, or two M20 x 1.5 cable glands.