Versa-Tech Single Phase Vacuum Recloser with Embedded Control, 29.3 kV, 125 kV BIL, up to 400 A
Versa-Tech single phase reclosers pair embedded microprocessor control with power drawn from the line, for tap points on overhead medium voltage distribution networks. The unit sits at line potential and is isolated from earth by a polymer support insulator, so no earthing is required.
- Type
- single phase vacuum recloser with embedded control
- Series
- Versa-Tech (VTLT, VTI, VTII, VT-XC)
- Rated voltage
- 29.3 kV
- BIL
- 125 kV
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The VTLT model is rated for 100 A continuous current, interrupts 4 kA and allows 10,000 mechanical operations. The VTI and VTII share a 400 A continuous rating, an 8 kA interrupting capacity and up to 30,000 operations, and both withstand 8 kA for 3 seconds. The VT-XC keeps the same current and interrupting ratings but withstands 8 kA for only 0.5 seconds, and its Wi-Fi starts working from a 6A load. The first Versa-Tech generation appeared in 2007, and the range now comprises the VTLT, VTI, VTII and VT-XC.
Everything sits at line potential, isolated from earth by a polymer support insulator, so earthing is not needed. Interruption is carried out by a vacuum chamber with a magnetic actuator, and a microcontroller runs the protection. The recloser is self-powered from line current and can be reached over a wireless link for its settings. Routine maintenance is not required, and the unit carries a lockout indicator and an operations counter.
Radio on the 900MHz band is available for the VTI, VTLT and VTII from a 10A load, and Wi-Fi works at up to 100 feet. Memory stores 11 legacy, 4 ANSI, 1 IEEE, 5 IEC and 4 user-defined time-current curves, along with up to 10 settings profiles and a Non-Reclose / Hot Line Tag function. SCADA communication uses DNP3, and cellular LTE Cat-M1 modem support is available on the VT-XC.
The operating range runs from -40 to 60°C, and the battery is rated for a 10 year shelf life, with replacement every 6 to 8 years. The unit fixes with a 5/8 inch (15mm) bolt and an 11 inch (27.9cm) nominal hole spacing. The design conforms to IEEE C37.60-2003 and IEEE 1686-2007, with the VTII also meeting IEEE C37.231-2006, and production is certified to ISO 9001:2015.
Technical specifications
| Type | single phase vacuum recloser with embedded control |
|---|---|
| Series | Versa-Tech (VTLT, VTI, VTII, VT-XC) |
| Rated voltage | 29.3 kV |
| BIL | 125 kV |
| Frequency | 60 Hz |
| Continuous current | 100 A (VTLT), 400 A (VTI, VTII, VT-XC) |
| Interrupting current | 4 kA (VTLT), 8 kA (VTI, VTII, VT-XC) |
| Mechanical life | 10000 (VTLT), 30000 operations |
| Minimum trip current | 30–200 A (VTLT), 30–800 A |
| Withstand current | 3 s at 8 kA (VTI, VTII), 0.5 s at 8 kA (VT-XC) |
| Creepage distance | 39.4 in |
| Communication | Wi-Fi up to 100 feet, 900MHz radio, LTE Cat-M1 (VT-XC) |
| SCADA protocol | DNP3 |
| Time-current curves | 11 legacy, 4 ANSI, 1 IEEE, 5 IEC, 4 user-defined |
| Settings profiles | up to 10 |
| Operating temperature | -40 to 60°C |
| Mounting | 5/8 in (15mm) bolt, 11 in (27.9cm) between holes |
| Standards | IEEE C37.60-2003, IEEE 1686-2007, IEEE C37.231-2006, ISO 9001:2015 |
Part numbers
Show all part numbers (13)
VTLT, VTI, VTII, VT-XC, PSC8620064, PSC8620253, PSC8620255, PSC8620397, PSC8620482, C1SPR3418VT, C3SPR3418VT, C3SPR3418VTLU, C3MW24ML
Request a price and lead time
Versa-Tech Single Phase Vacuum Recloser with Embedded Control, 29.3 kV, 125 kV BIL, up to 400 A. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Does a Versa-Tech recloser need an earth connection?
No. The unit is held at line potential and isolated from earth by a polymer support insulator, and the manufacturer does not require earthing.
How does the VT-XC differ from the VTI?
The VT-XC starts Wi-Fi from a 6A load and supports a cellular LTE Cat-M1 modem. It withstands 8 kA for 0.5 seconds, compared with 3 seconds for the VTI.
Which model suits a branch carrying up to 100 A?
The VTLT is rated at 100 A with a 4 kA interrupting capacity and a 30–200 A trip range. For loads up to 400 A and fault currents up to 8 kA, the VTI, VTII or VT-XC are used instead.