SmartClose Synchronous Vacuum Capacitor Switch, Three-Phase, 15 and 27 kV, 200 A and 400 A
SmartClose energises a capacitor bank in step with the voltage waveform, closing at zero voltage, which reduces transient overvoltages and charging currents. The three-phase tank switch has three 120 VAC solenoid mechanisms, six built-in voltage sensors and conforms to ANSI C37.66-2005.
- Type
- synchronous vacuum capacitor switch
- Phases
- three-phase, tank-mounted
- Rated voltage
- 15 kV / 27 kV
- Insulation level
- 110 kV BIL / 125 kV BIL
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
A discharged capacitor bank is charged from almost zero potential up to line voltage in the instant it is switched in. For several cycles after switching, transient overvoltages and large charging currents persist, which can blow fuses and interrupt customers, especially with large banks or with banks switched close to one another. Closing synchronously at zero voltage substantially reduces these transients.
The bank controller decides when the bank is needed. The switch receives the command and carries out the synchronous closing itself, timed to the waveform. It self-calibrates, switches without re-strikes and needs no maintenance. Synchronous switching shortens the time, complexity and cost of bringing the bank into service.
The switch is three-phase and sits in a tank. Three 120 VAC solenoid mechanisms allow the poles to be operated independently where required, and each pole has a manual handle for opening and closing. The design includes six built-in voltage sensors, a mounting flange for a substation frame, a 5-pin socket for the control cable, and a fibre-optic compartment with 2 connectors for optical cables. The insulation is cycloaliphatic epoxy, and animal guards are supplied in the kit.
The variants are SMC15-110D1D2ME6XX for 15 kV, 110 kV BIL and 200 A with 18 in creepage; SMC15-110D1D2MEAXX with the same ratings and 33 in creepage; SMC15-110E1D2ME6XX at 400 A with 18 in creepage; SMC27-125D1D2ME6XX for 27 kV, 125 kV BIL and 200 A with 18 in creepage; SMC27-125D1D2MEAXX with 33 in creepage; and SMC27-125E1D2ME6XX at 400 A with 18 in creepage.
The switch is intended for capacitor banks on poles and for banks in cabinets on a pad in 15 kV and 27 kV networks. The control circuit operates at 120 VAC, the switch type is synchronous vacuum, and the mechanism is solenoid. For substation frame mounting the standard flange is used, and commands from the bank controller arrive over the control cable.
Technical specifications
| Type | synchronous vacuum capacitor switch |
|---|---|
| Phases | three-phase, tank-mounted |
| Rated voltage | 15 kV / 27 kV |
| Insulation level | 110 kV BIL / 125 kV BIL |
| Rated current | 200 A / 400 A |
| Creepage distance | 18 in or 33 in |
| Drive | solenoid, 3 x 120 VAC, independent pole control |
| Manual operation | 3 handles for opening and closing |
| Voltage sensors | 6 built-in |
| Insulation | cycloaliphatic epoxy |
| Connections | 5-pin socket, fibre-optic compartment with 2 connectors |
| Mounting | flange for substation frame |
| Standard | ANSI C37.66-2005 |
Part numbers
Show all part numbers (6)
SMC15-110D1D2ME6XX, SMC15-110D1D2MEAXX, SMC15-110E1D2ME6XX, SMC27-125D1D2ME6XX, SMC27-125E1D2ME6XX, SMC27-125D1D2MEAXX
Request a price and lead time
SmartClose Synchronous Vacuum Capacitor Switch, Three-Phase, 15 and 27 kV, 200 A and 400 A. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Who decides when the bank is switched in?
The bank controller sends the command, and the switch performs the synchronous closing itself, timed to the voltage waveform.
Can the poles be operated separately?
Yes. Each pole has its own 120 VAC solenoid drive, so the poles can be controlled independently where required.
Which versions are rated 400 A?
SMC15-110E1D2ME6XX at 15 kV, 110 kV BIL and SMC27-125E1D2ME6XX at 27 kV, 125 kV BIL, both with 18 in creepage.
Similar equipment from other manufacturers