PRS Single-Phase Programmable Sectionaliser, 15, 27 and 38 kV, 300 A
The single-phase PRS sectionaliser tells temporary faults from permanent ones and trips a lateral only after a preset number of trips by a backup recloser or circuit breaker with auto-reclosing. It mounts in the base of a fuse cutout, is programmed over USB and returns to service once it has tripped.
- Type
- single-phase programmable resettable sectionaliser
- Rated voltage (BIL)
- 15 kV (110 kV BIL), 27 kV (125 kV BIL), 38 kV (150/170 kV BIL)
- Continuous current rating
- 300 A
- Frequency
- 60 Hz / 50 Hz
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The sectionaliser protects single-phase laterals of overhead distribution lines. It is installed at the start of the lateral, where it works alongside a backup automatic recloser or a circuit breaker with auto-reclosing. The device distinguishes temporary (transient) faults from permanent ones and opens the lateral only for a permanent fault, so customers on the main line do not lose supply through unnecessary trips.
Typical uses include sections where fuses are hard to coordinate, lines with too little load to justify a recloser, and remote locations where animals and vegetation cause temporary faults. It also helps to reduce the SAIDI index. A single programmable unit covers these tasks within its voltage class.
The number of counts (1, 2, 3 or 4), the minimum trip current between 10 and 480 A and the reset time from 30 to 300 seconds in 1-second steps are all programmable. The minimum line current is 5 A. Inrush is detected in under one cycle using a fast Fourier transform (FFT), which recognises both symmetrical and asymmetrical inrush currents. The dead-line threshold is 200 mA or less, detected in 100 ms (± 20 ms), and the total operating time including that detection is 400 ms. The device keeps an event history for analysing network performance.
Ratings are 15 kV (110 kV BIL), 27 kV (125 kV BIL) and 38 kV (150/170 kV BIL), with a continuous current of 300 A at 60 Hz or 50 Hz. Short-time withstand is 8600 A symmetrical for 15 cycles, 4000 A symmetrical for 1 second and 3200 A symmetrical for 3 seconds, and the momentary rating is 12000 A asymmetrical. Current measurement accuracy is ±5%, surge withstand is 65 kA to ANSI C37.63, electromagnetic interference is controlled to ANSI C37.90.2, the ingress protection is IP68, and the operating range is -40 to +60 °C.
The sectionaliser is supplied with a polymer or porcelain cutout base. The air-reset hinge lets the device return to service in the base itself, without a wrench. A version with an arc-quenching chamber, which opens under rated load, is offered alongside a version without one. For setup, a USB cable from the kit connects to a port at the bottom of the housing and to a computer running the configuration software, which suggests settings based on the parameters of the upstream device.
Technical specifications
| Type | single-phase programmable resettable sectionaliser |
|---|---|
| Rated voltage (BIL) | 15 kV (110 kV BIL), 27 kV (125 kV BIL), 38 kV (150/170 kV BIL) |
| Continuous current rating | 300 A |
| Frequency | 60 Hz / 50 Hz |
| Minimum line current | 5 A |
| Minimum actuating current | programmable, 10 to 480 A |
| Number of counts | 1, 2, 3 or 4 |
| Reset time | 30 to 300 s, 1 s steps |
| Inrush detection | under 1 cycle, FFT |
| Dead-line threshold | 200 mA or less |
| Dead-line detection time | 100 ms (± 20 ms) |
| Total operating time | 400 ms |
| Short-time withstand | 8600 A sym. (15 cycles), 4000 A sym. (1 s), 3200 A sym. (3 s) |
| Momentary current | 12000 A asym. |
| Current measurement accuracy | ± 5 % |
| Surge current withstand | 65 kA per ANSI C37.63 |
| Ingress protection | IP68 |
| Temperature range | -40 to +60 °C |
| Base | polymer or porcelain |
Part numbers
Show all part numbers (2)
CP7XXXXXXXXXX, C7XXXXXXXXXX
Request a price and lead time
PRS Single-Phase Programmable Sectionaliser, 15, 27 and 38 kV, 300 A. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which devices does the sectionaliser coordinate with?
It coordinates with a backup automatic recloser or a circuit breaker with auto-reclosing. The number of counts is set from 1 to 4, and the trip current from 10 to 480 A.
Does the sectionaliser have to be removed after it trips?
No. The air-reset hinge allows the device to be returned to service in the cutout base, without a wrench.
Can the PRS be opened under load?
Yes. The version with an arc-quenching chamber opens under the rated load of 300 A.