International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

LineDefender single-phase vacuum recloser up to 29.3 kV, 40, 100 and 200 A, fuse holder mount

LineDefender is a single-phase recloser for medium-voltage distribution networks up to 29.3 kV, installed in a fuse holder in place of a fuse link. It interrupts current in a vacuum chamber with magnetic actuation, is controlled by a programmable electronic unit and communicates by cellular SCADA modem, WiFi, Bluetooth or serial port.

Model
LineDefender
Type
single-phase recloser, magnetic vacuum interruption
Voltage class
up to 29.3 kV
BIL
125 kV

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The LineDefender recloser is intended for branches of overhead medium-voltage distribution lines up to 29.3 kV. It is mounted in a Powerfuse holder in place of a fuse link. After a temporary fault, the device carries out automatic reclosing cycles, so that a sustained outage does not occur. The design requires no maintenance, which is why the recloser suits the end sections of a network where fuse links were previously fitted.

Current is interrupted in a vacuum chamber with a magnetic actuator, and the operating logic is set by a programmable electronic control unit. After lockout at the end of the reclosing sequence, the device stays in its holder. It can be returned to service from the ground with a standard insulating pole by turning the yellow handle. The load is carried by the vacuum chamber, so personnel are not exposed to the arc.

A tripped recloser is visible from a distance, with a bright amber flashing beacon and a wide-angle reflective indicator that is noticeable by day and by night. For remote monitoring a cellular SCADA modem is available, and for local connection there are WiFi, Bluetooth or a serial interface. A built-in GPS helps analyse data from several devices. Settings are created and commissioned with the manufacturer's software platform.

The voltage class is up to 29.3 kV, with a BIL of 125 kV. The continuous rated currents are 40 A, 100 A and 200 A. The interrupting rating is 6.3 kA for the 100 A and 200 A versions and 3 kA for the 40 A version. The housing is made of all-weather aluminium, and the bushing is of CEP cycloaliphatic epoxy resin.

The current rating is chosen according to the load of the branch and the short-circuit current levels at the installation point. Before installation, check that the holder on the pole is compatible with the Powerfuse mounting.

Technical specifications

ModelLineDefender
Typesingle-phase recloser, magnetic vacuum interruption
Voltage classup to 29.3 kV
BIL125 kV
Continuous rated current40 A, 100 A, 200 A
Interrupting rating (100 A and 200 A)6.3 kA
Interrupting rating (40 A)3 kA
Controlprogrammable electronic
Communicationcellular SCADA modem, WiFi, Bluetooth, serial port, GPS
Housingaluminium, all-weather
BushingCEP
Indicationbeacon and wide-angle reflective semaphore
MountingPowerfuse holder

Request a price and lead time

LineDefender single-phase vacuum recloser up to 29.3 kV, 40, 100 and 200 A, fuse holder mount. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Can the recloser be installed in place of a fuse link?

Yes. LineDefender is mounted in a Powerfuse holder in place of the fuse link, and it stays in the holder after lockout.

How is the recloser returned to service after lockout?

It is closed from the ground with a standard insulating pole by turning the yellow handle.

What interrupting rating applies to each version?

6.3 kA for the 100 A and 200 A versions, and 3 kA for the 40 A version.

Similar equipment from other manufacturers