Liberty Three Phase Ganged Load Break Switch 27 kV, 630 A
The Liberty three-phase load break switch is for overhead distribution lines up to 27 kV. Three vacuum interrupter modules, operated by one common ganged mechanism, sit in a single solid-insulated housing rated at 630 A with a 150 kV impulse withstand.
- Type
- overhead switch with solid dielectric
- Number of phases
- 3, ganged operation
- Maximum voltage
- 27 kV
- Impulse withstand (BIL)
- 150 kV
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The Liberty load break switch is installed on overhead distribution lines for three-phase sectionalising and for switching load current. It belongs to the family of overhead switches with solid dielectric and works in networks with a maximum voltage of 27 kV at 50/60 Hz, with a rated current of 630 A.
Three vacuum interrupters share one ganged operating mechanism inside the housing. Arcs are quenched in vacuum and the live parts are insulated by solid dielectric, so the switch contains neither oil nor insulating gas. According to the manufacturer it requires no maintenance. The housing is welded and riveted stainless steel, finished in ANSI 70 colour over a zinc primer for mechanical strength and corrosion resistance.
Sensors built into the switch send data to a controller for distribution network automation systems. All signals and controls are brought out through a single 32-pin connector, which links the unit to a control cabinet by cable. A semaphore indicator shows the contact position and a mechanical counter records operations. A manual operating and locking handle is also fitted.
The nominal ratings are 27 kV, 630 A and 150 kV BIL. The compact and light design is meant for mounting directly on the pole of an overhead line. The switch can also be supplied as a complete kit for site installation: controllers, cables and switching devices are assembled, configured, combined into one system and tested before shipment to the customer’s requirements. On site this leaves only mechanical mounting and connection of the lines.
Technical specifications
| Type | overhead switch with solid dielectric |
|---|---|
| Number of phases | 3, ganged operation |
| Maximum voltage | 27 kV |
| Impulse withstand (BIL) | 150 kV |
| Rated current | 630 A |
| Frequency | 50/60 Hz |
| Arc quenching | vacuum interrupter chambers |
| Housing | stainless steel, ANSI 70 paint over zinc primer |
| Control connector | one, 32-pin |
| Indication | semaphore, mechanical operations counter |
| Manual operation | operating and locking handle |
Request a price and lead time
Liberty Three Phase Ganged Load Break Switch 27 kV, 630 A. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What is the Liberty switch used for?
Three-phase sectionalising and switching of load current on overhead lines up to 27 kV and 630 A.
Can the switch be operated remotely?
Yes. Built-in sensors and controls are brought out to a 32-pin connector for a cabinet with a controller. A manual operating and locking handle is also fitted to the unit.
Does the arc quenching medium need servicing?
No. Arcs are quenched in vacuum interrupters with solid insulation, the unit contains no oil or gas, and the manufacturer states that it needs no maintenance.