Liberty IPR independent phase recloser 27 kV, 800 A, 16 kA

The Liberty IPR consists of three single-phase vacuum reclosers for overhead lines up to 27 kV. It has a rated current of 800 A and a rated symmetrical short-circuit current of 16 kA, and each phase carries two voltage sensors and one current sensor.

Rated voltage
27 kV
Rated frequency
50/60 Hz
Rated continuous current
800 A RMS
8-hour overload capacity
960 A RMS

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The Liberty IPR (Independent Phase Recloser) is used for distribution network automation, for interrupting three-phase short circuits and for overcurrent protection on one or three phases. According to the manufacturer, its applications include utility networks, renewable energy facilities, and industrial and commercial sites with voltages up to 27 kV.

Each phase has its own tank with a vacuum interrupter cast in hydrophobic cycloaliphatic epoxy resin, and a magnetic actuator. Solid insulation lowers the risk of flashover in polluted surroundings, and no maintenance is needed. The tank base is stainless steel and the tank is earthed. The mechanical endurance is at least 10000 operations.

The system carries 6 voltage sensors and 3 current sensors, so each phase has two voltage sensors and one current sensor. Every unit has an angled 32-pin bayonet connector with a turn lock. The recloser is compatible with industrial recloser controllers in cabinets with a 32- or 42-pin interface. Three operating modes are provided: single-phase trip with three-phase lockout, three-phase trip with three-phase lockout, and single-phase trip with single-phase lockout. Each unit has a manual handle for opening, closing and locking, which can be worked from the ground with an insulated pole, and a semaphore shows the contact position.

Mounting options are a central or side bracket on a pole, cluster arrangement, crossarm mounting and a phase-over-phase layout. The frames have provision for surge arresters and station service transformers, which can be supplied already fitted. NEMA line terminals with 2 or 4 holes and clamp-type terminals are available for connecting conductors. Switching performance was tested to IEEE / IEC C37.60/62271-111:2019. The operating temperature range is -40°C to +60°C, and the weight of the three units without frame is 294 lb (133 kg).

Technical specifications

Rated voltage27 kV
Rated frequency50/60 Hz
Rated continuous current800 A RMS
8-hour overload capacity960 A RMS
Rated symmetrical short-circuit current16 kA
Peak current, asymmetrical41.6 kA
Impulse withstand voltage (BIL)150 kV
Power frequency withstand voltage, dry60 kV
Power frequency withstand voltage, wet50 kV
Mechanical enduranceat least 10000 operations
Temperature range-40°C to +60°C
Weight of three units (without frame)294 lb (133 kg)
Sensors per system6 voltage, 3 current
Connector32-pin
Test standardIEEE / IEC C37.60/62271-111:2019

Request a price and lead time

Liberty IPR independent phase recloser 27 kV, 800 A, 16 kA. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Can the Liberty IPR interrupt a single phase only?

Yes. Single-phase trip modes are supported with either single-phase or three-phase lockout, as well as three-phase trip with three-phase lockout.

Which controllers can be connected?

The recloser is compatible with industrial recloser controllers in cabinets with a 32- or 42-pin interface, and each unit has a 32-pin connector.

Which mounting options are provided on a pole?

A central or side bracket on a pole, cluster arrangement, crossarm mounting and a phase-over-phase layout.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides