
CSD Single-Phase Oil-Filled Capacitor Switch, 15 and 20 kV, 200 A and 90 A, Motor Drive
CSD oil-filled switches switch capacitor banks on poles and on pads. The CSD15 is rated 15 kV and 200 A with 95 and 125 kV BIL versions, while the CSD20 is rated 20 kV with a continuous current of 90 A, and both use a motor drive that can also be operated by hand.
- Type
- single-phase oil-filled capacitor switch
- Models
- CSD15, CSD20
- Maximum voltage
- 15 kV / 20 kV
- Rated voltage class
- 14.4 kV / 19.9 kV
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
These single-phase switches have motor drives and are intended for 15 kV and 25 kV distribution networks, as well as 35 kV networks with a grounded wye configuration. They operate in capacitor banks on poles and on pads and conform to ANSI C37.66. The oil interruption design has been proven by long field service.
The tank is corrosion-resistant steel, finished with grey polyurethane paint. Porcelain bushings have creepage distances of 11, 17 or 24 in and offer low radio interference. Internal and external insulation levels are the same for both models. The ratings are engraved on an aluminium plate, and the external fasteners are stainless steel, aluminium or plated brass. Access to the mechanism requires removing four bolts. The yellow manual operating lever is covered by a weather shield but remains fully accessible.
The switch has a 5-pin socket and a built-in NEMA bracket. Mounting on a pole, wall or frame needs no extra wiring or fixings, and mounting kits are available for crossarms. Control can be manual or automatic from a capacitor bank controller or a similar device.
The CSD15 has a maximum voltage of 15 kV, a rated voltage class of 14.4 kV, a BIL of 95/125 kV and a continuous and capacitive current of 200 A. Its withstand values are 35/45 kV for one minute dry and 30/40 kV for 10 seconds under rain. The CSD20 has 20 kV, a class of 19.9 kV, a BIL of 125 kV, withstand values of 60 kV and 40 kV, and a current of 90 A. Both models have a momentary current of 9000 A asymmetrical, a high-frequency making current of 12000 A peak and an operating time of 2.5/4.0 s. The CSD15 control voltage is 120 VAC (100–130 V) or 240 VAC (210–250 V), while the CSD20 uses 120 VAC at 50/60 Hz, with a motor current of 2.8 A. The weight with oil is 37 and 39 lb, and the oil volume is 1.5 gallons.
The three versions are 33050001 (CSD15-95, 200 A, 11 in bushings), 33078601 (CSD15-125, 200 A, 17 in bushings) and 33184601 (CSD20-125, 90 A, 17 in bushings). The last two digits of the part number are replaced by an auxiliary contact code: 02 for Form C with a common neutral for low-voltage supply, 04 for dry Form A (normally open), 07 for dry Form C with a 6-pin socket and 15 for dry Form B (normally closed). The 33078601 measures 13.000 in x 15.500 in x 27.500 in.
Technical specifications
| Type | single-phase oil-filled capacitor switch |
|---|---|
| Models | CSD15, CSD20 |
| Maximum voltage | 15 kV / 20 kV |
| Rated voltage class | 14.4 kV / 19.9 kV |
| Insulation level | 95/125 kV BIL / 125 kV BIL |
| Continuous and capacitive current | 200 A / 90 A |
| Momentary current | 9000 A asym. |
| Short-time current | 6000 A sym. (1/2 s), 4500 A sym. (1 s) |
| High-frequency making current | 12000 A peak |
| Control voltage | 120 VAC (100–130), 240 VAC (210–250), 50/60 Hz |
| Motor current | 2.8 A |
| Operating time | 2.5/4.0 s |
| Weight with oil | 37 / 39 lb |
| Oil volume | 1.5 gallons |
| Bushing creepage distance | 11, 17, 24 in |
| Standard | ANSI C37.66 |
Part numbers
Show all part numbers (3)
33050001, 33078601, 33184601
Request a price and lead time
CSD Single-Phase Oil-Filled Capacitor Switch, 15 and 20 kV, 200 A and 90 A, Motor Drive. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which model should be chosen for a 20 kV network?
The CSD20-125 (part number 33184601) is rated 20 kV and 125 kV BIL, with a continuous current of 90 A and 17 in bushings.
How are switches with auxiliary contacts ordered?
The last two digits of the part number are replaced by an option code, 02, 04, 07 or 15, depending on whether Form A, B or C contacts are required.
How is the switch mounted?
It is mounted on a pole, wall or frame through its built-in NEMA bracket, without extra wiring, and separate kits are available for crossarms.
Similar equipment from other manufacturers






