BPFR11P Fused Bypass Switch, Right-Hand Opening, 15 kV, 110 kV BIL, 600 A, 100 A Fuse

The BPFR11P is a BPF bypass switch for bypassing and isolating substation reclosers during planned maintenance. A 600 A load switch is connected in series with a Type C fuse, which protects the line against overcurrent while the recloser is out of service.

Type
Fused bypass load switch
Maximum voltage
15 kV
Minimum reference voltage
14.4 kV
BIL
110 kV

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

BPF bypass switches are installed alongside a recloser at a distribution substation. During maintenance the recloser is bypassed and isolated, and the line is supplied through the bypass circuit with its fuse. A separately mounted M3S disconnector is usually fitted alongside the BPF. Operation is carried out with an insulated operating pole.

The construction consists of a 600 A load switch and a Type C fuse holder connected in series. Both devices are mounted on a common mounting channel, so they are installed as a single assembly. In the BPFR11P version the 100 A fuse holder is on the right, and the series also offers a left-hand fuse holder position and 200 A fuse holders. Station-class insulators are in Sky Grey porcelain, the blade is solid copper in a two-blade truss-member design, and the contacts are silver-plated. The base is steel galvanised to ASTM A153.

The rating is 15 kV maximum with a minimum reference voltage of 14.4 kV, and a basic insulation level (BIL) of 110 kV. The creepage distance is 393.7 mm and the interrupting rating is 10,000 A. The switch circuit withstands 25 kA symmetrical for 1 second and 65 kA peak for 10 cycles, and it allows an emergency overload of 1080 A for 8 hours. The maximum temperature rise is 25.7 °C in the switch circuit at 600 A and 15.9 °C in the fuse circuit.

The fuse holder has a single-vent design with a solid cap and takes universal fuse links, and the internal arc-quenching liner is made of synthetic material. The replacement fuse holder is designated T710-112T. The switch complies with ANSI/IEEE C37.41 and C37.42 (2016 edition) and other applicable ANSI/IEEE standards. The BPF series is also produced at 27 kV with a 150 kV BIL.

Technical specifications

TypeFused bypass load switch
Maximum voltage15 kV
Minimum reference voltage14.4 kV
BIL110 kV
Switch rated current600 A
Fuse holderType C, 100 A, right-hand
Interrupting rating10,000 A
Short-time withstand current25 kA symmetrical, 1 second
Peak withstand current65 kA peak, 10 cycles
Emergency overload1080 A, 8 hours
Temperature rise, switch circuit at 600 A25.7 °C
Temperature rise, fuse circuit15.9 °C
Creepage distance393.7 mm
BladeSolid copper, two-blade truss-member design
ContactsSilver-plated
BaseGalvanised steel, ASTM A153
Insulator colourSky Grey
Replacement fuse holderT710-112T
StandardsANSI/IEEE C37.41, C37.42, 2016 edition

Part numbers

Show all part numbers (1)

BPFR11P

Request a price and lead time

BPFR11P Fused Bypass Switch, Right-Hand Opening, 15 kV, 110 kV BIL, 600 A, 100 A Fuse. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Is the line protected against overcurrent while the recloser is out of service?

Yes, a Type C fuse rated 100 A is connected in series with the switch in the bypass circuit.

Which replacement fuse holder fits the BPFR11P?

The replacement fuse holder is designated T710-112T.

Are versions with a left-hand fuse holder or a larger current available?

Yes, the BPF series has left-hand and right-hand fuse holder positions, with 100 A and 200 A fuse holders.