AR114FM Three-Phase Gang Operated Loadbreak Switch, 27 kV, 150 kV BIL, 900 A
The AR114 switch, part number AR114FM, is a loadbreak switch for overhead lines and substations with a maximum voltage of 27 kV and a rated current of 900 A. All three phases are operated by one gang mechanism, the blades open clockwise and the insulators are dark grey polymer.
- Type
- Horizontal three-phase gang operated loadbreak switch
- Maximum voltage
- 27 kV
- BIL
- 150 kV
- Rated current
- 900 A
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The switch breaks load currents on distribution networks, in substations and on transmission lines. This horizontal three-phase version is gang operated, so all three phases switch together. It has a 150 kV lightning impulse insulation level (BIL), a maximum voltage of 27 kV and a rated current of 900 A, with an emergency overload of 1080 A for 8 hours. The switch complies with applicable ANSI/IEEE standards.
The blades are solid copper, single-member, and the contacts are silver plated. The interphase shaft is made of fibreglass. The polymer insulators have a 2 1/4 in bolt circle and a 28 in creepage distance, with a 10 in dry arc distance. The arc interrupter can be replaced using assembly C818-0001. Each three-phase switch has a four-link mechanism with an over-centre action, which holds the blades in the closed position, reduces the force needed at the operator and gives a clear snap at the end of travel.
Operation can be by a rotary or linear operator, or by an operating rod, either with a full rod run along the pole or from a crossarm. The rod option shortens installation time, reduces the risk of vandalism and needs no linkage adjustment. The configuration is set by positions 4 to 13 of the catalogue number, according to the manufacturer's numbering system.
Switching capacity is 50 operations at 600 A and 10 operations at 900 A, with loop switching at 600 A, magnetising current switching for a 2500 kVA transformer, and charging current of 20 A for shielded cable and 10 A for unshielded cable. The switch withstands 25 kA asymmetrical once and 20 kA asymmetrical three times, with a short-time rating of 25 kA symmetrical for 3 seconds and a peak of 65 kA. Temperature rise is no more than 30.9 °C at 600 A and 47.5 °C at 900 A.
For pole calculations, the mechanical ratings are an insulator cantilever bending strength of 1200 lb (5.34 kN) under routine testing, a torsional strength of 3000 in lb (339 N-M) and a tension range of 5000 lb. The dead-end working load is 8000 lb and 700 lb under unequal load. The switch is rated for operation with ice up to 3/4 in thick. Dimensions given by the manufacturer apply to the installed condition.
Technical specifications
| Type | Horizontal three-phase gang operated loadbreak switch |
|---|---|
| Maximum voltage | 27 kV |
| BIL | 150 kV |
| Rated current | 900 A |
| Emergency overload, 8 hours | 1080 A |
| Loop switching | 600 A |
| Magnetising current switching | 2500 kVA |
| Cable charging current, shielded / unshielded | 20 A / 10 A |
| Switching endurance | 50 operations at 600 A, 10 operations at 900 A |
| Fault current | 25 kA asymmetrical (once), 20 kA asymmetrical (three times) |
| Short-time withstand, 3 s | 25 kA symmetrical |
| Peak withstand | 65 kA |
| Creepage distance | 28 in |
| Dry arc distance | 10 in |
| Blades / contacts | Solid copper / silver |
| Insulators | Polymer, 2 1/4 in bolt circle, dark grey |
| Cantilever bending strength | 1200 lb (5.34 kN) |
| Torsional strength | 3000 in lb (339 N-M) |
| Standards | ANSI/IEEE |
Part numbers
Show all part numbers (1)
AR114FM
Request a price and lead time
AR114FM Three-Phase Gang Operated Loadbreak Switch, 27 kV, 150 kV BIL, 900 A. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How many load break operations can the switch carry?
The switch is rated for 50 operations at 600 A and 10 operations at 900 A. An assembly C818-0001 is provided for replacing the arc interrupter.
How can the switch be operated?
By a rotary or linear operator, or by an operating rod, either with the rod running the full length of the pole or from a crossarm.
Can the switch be used to disconnect an unloaded transformer and cable?
Yes, it is rated for magnetising current switching up to 2500 kVA and charging current of 20 A for shielded cable and 10 A for unshielded cable.