AIS air-insulated pad-mounted switchgear for 15 and 25 kV networks, 600 A
AIS is a pad-mounted outdoor switchgear unit for sectionalising 15 and 25 kV cable networks. It combines air insulation with fully enclosed live parts (deadfront) and a sealed switching compartment. The versions differ in the number of phases and of switching and fuse ways.
- Type
- air-insulated, deadfront, pad-mounted
- Rated voltage
- 15 kV / 25 kV
- Maximum voltage
- 15.5 kV / 29 kV
- BIL
- 95 kV / 125 kV
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The AIS unit is installed in underground distribution networks of 15 and 25 kV to disconnect, sectionalise and isolate sections of cable lines. Functionally, the switch ways are load break switches with arc-quenching chambers, fitted in a metal enclosure on a foundation. Fuse ways protect the outgoing cables, and the switching ways transfer supply between directions.
The construction is of deadfront type: all live parts are enclosed, cables connect through separable connectors, the switching compartment is sealed and the insulating medium is air. This reduces access to live parts by personnel and by outsiders, and reduces the number of outages caused by vegetation or animals. On the front panel are 600 A bushings, with 200 A sockets available to order, and they can be replaced from outside without dismantling the panel. Enlarged viewing windows show the position of the 600 A switch and the state of the fuses, with a separate window provided for a fault indicator.
The enclosure is welded from 11 gauge steel, and a 304 stainless steel version is available for aggressive environments. The surface undergoes multi-stage chemical cleaning and powder coating, and the coating conforms to ANSI/IEEE C57.12.28. Louvres in the enclosure stop gases and moisture from accumulating, and an inner ceiling coating prevents condensation. Built-in spacers under the base increase the clearance for the door, and there is no central door post, so the cable compartments have more room. The doors have a three-point lock, a pentagonal latch and space for a padlock, and an operating handle is kept in each control compartment.
The range includes three-phase versions AIS-3, AIS-5, AIS-6, AIS-9, AIS-10, AIS-11, AIS-12 and AIS-13A, with different combinations of switch and fuse ways, the single-phase AIS-1A with two supply sources, and the motor-operated AIS-MO with four ways. The motor-operated version is used for remote control, telecontrol, automatic source transfer and line status reporting, and it can take telemetry units, current and voltage sensors and a station service transformer.
The unit is dimensionally compatible with foundations used for comparable equipment, and transition bases are available for foundations fitted to equipment with open live parts. Installation is carried out on a ready-made slab, and earthing is made through a 3/8 inch rod.
Technical specifications
| Type | air-insulated, deadfront, pad-mounted |
|---|---|
| Rated voltage | 15 kV / 25 kV |
| Maximum voltage | 15.5 kV / 29 kV |
| BIL | 95 kV / 125 kV |
| Withstand voltage | 35 kV / 60 kV at 60 Hz |
| Load current | 600 A / 600 A |
| Continuous current, switch side | 600 A |
| Maximum current, fuse side | 200 A / 200 A |
| Magnetising current switched | 21 A / 21 A |
| Peak withstand current (asymmetrical) | 41200 A |
| Short-time withstand current (1 s) | 18600 A |
| Fault current, 1 time | 42700 A |
| Structural load (design / test) | 1750 lb / 2500 lb |
| Enclosure | 11 gauge steel; optional 304 stainless steel |
| Coating | powder coated, ANSI/IEEE C57.12.28 |
| Bushings | 600 A, or 200 A sockets; replaceable from outside |
Part numbers
Show all part numbers (10)
AIS-MO, AIS-10, AIS-11, AIS-12, AIS-1A, AIS-3, AIS-13A, AIS-6, AIS-9, AIS-5
Request a price and lead time
AIS air-insulated pad-mounted switchgear for 15 and 25 kV networks, 600 A. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Can a bushing be replaced on site?
Yes. The 600 A bushings on the switch ways are replaced from outside without dismantling the front panel, and 200 A sockets can be ordered instead.
Which version is needed for automatic source transfer?
The AIS-MO motor-operated version with four ways for 15 and 25 kV. It can be fitted with telecontrol units, current and voltage sensors and a station service transformer.
Will the unit fit an existing foundation?
It is dimensionally compatible with foundations used for comparable equipment, and transition bases are available for foundations fitted to equipment with open live parts.