International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

AIS air-insulated pad-mounted switchgear for 15 and 25 kV networks, 600 A

AIS is a pad-mounted outdoor switchgear unit for sectionalising 15 and 25 kV cable networks. It combines air insulation with fully enclosed live parts (deadfront) and a sealed switching compartment. The versions differ in the number of phases and of switching and fuse ways.

Type
air-insulated, deadfront, pad-mounted
Rated voltage
15 kV / 25 kV
Maximum voltage
15.5 kV / 29 kV
BIL
95 kV / 125 kV

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The AIS unit is installed in underground distribution networks of 15 and 25 kV to disconnect, sectionalise and isolate sections of cable lines. Functionally, the switch ways are load break switches with arc-quenching chambers, fitted in a metal enclosure on a foundation. Fuse ways protect the outgoing cables, and the switching ways transfer supply between directions.

The construction is of deadfront type: all live parts are enclosed, cables connect through separable connectors, the switching compartment is sealed and the insulating medium is air. This reduces access to live parts by personnel and by outsiders, and reduces the number of outages caused by vegetation or animals. On the front panel are 600 A bushings, with 200 A sockets available to order, and they can be replaced from outside without dismantling the panel. Enlarged viewing windows show the position of the 600 A switch and the state of the fuses, with a separate window provided for a fault indicator.

The enclosure is welded from 11 gauge steel, and a 304 stainless steel version is available for aggressive environments. The surface undergoes multi-stage chemical cleaning and powder coating, and the coating conforms to ANSI/IEEE C57.12.28. Louvres in the enclosure stop gases and moisture from accumulating, and an inner ceiling coating prevents condensation. Built-in spacers under the base increase the clearance for the door, and there is no central door post, so the cable compartments have more room. The doors have a three-point lock, a pentagonal latch and space for a padlock, and an operating handle is kept in each control compartment.

The range includes three-phase versions AIS-3, AIS-5, AIS-6, AIS-9, AIS-10, AIS-11, AIS-12 and AIS-13A, with different combinations of switch and fuse ways, the single-phase AIS-1A with two supply sources, and the motor-operated AIS-MO with four ways. The motor-operated version is used for remote control, telecontrol, automatic source transfer and line status reporting, and it can take telemetry units, current and voltage sensors and a station service transformer.

The unit is dimensionally compatible with foundations used for comparable equipment, and transition bases are available for foundations fitted to equipment with open live parts. Installation is carried out on a ready-made slab, and earthing is made through a 3/8 inch rod.

Technical specifications

Typeair-insulated, deadfront, pad-mounted
Rated voltage15 kV / 25 kV
Maximum voltage15.5 kV / 29 kV
BIL95 kV / 125 kV
Withstand voltage35 kV / 60 kV at 60 Hz
Load current600 A / 600 A
Continuous current, switch side600 A
Maximum current, fuse side200 A / 200 A
Magnetising current switched21 A / 21 A
Peak withstand current (asymmetrical)41200 A
Short-time withstand current (1 s)18600 A
Fault current, 1 time42700 A
Structural load (design / test)1750 lb / 2500 lb
Enclosure11 gauge steel; optional 304 stainless steel
Coatingpowder coated, ANSI/IEEE C57.12.28
Bushings600 A, or 200 A sockets; replaceable from outside

Part numbers

Show all part numbers (10)

AIS-MO, AIS-10, AIS-11, AIS-12, AIS-1A, AIS-3, AIS-13A, AIS-6, AIS-9, AIS-5

Request a price and lead time

AIS air-insulated pad-mounted switchgear for 15 and 25 kV networks, 600 A. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Can a bushing be replaced on site?

Yes. The 600 A bushings on the switch ways are replaced from outside without dismantling the front panel, and 200 A sockets can be ordered instead.

Which version is needed for automatic source transfer?

The AIS-MO motor-operated version with four ways for 15 and 25 kV. It can be fitted with telecontrol units, current and voltage sensors and a station service transformer.

Will the unit fit an existing foundation?

It is dimensionally compatible with foundations used for comparable equipment, and transition bases are available for foundations fitted to equipment with open live parts.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides