C-LUX Series 6102 Compact LED Light Fittings, Ex db eb ib op is IIC T4 Gb, IP66/IP67
C-LUX Series 6102 are compact LED fittings for normal lighting or for emergency use together with exit signs. Marked Ex db eb ib op is IIC T4 Gb and Ex tb op is IIIC T100 °C Db for zones 1, 2, 21 and 22, with IP66/IP67 enclosure protection.
- Lamp
- LED
- Colour temperature
- 5000 K
- Luminous flux
- 490 ... 775
- Control interface
- without; DALI; Internal address module
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The C-LUX 6102 compact fittings serve as normal luminaires or as emergency luminaires, combined with emergency exit signs and/or an address module for central battery systems. They can be fixed to a wall or ceiling, or suspended. The body is lightweight and compact.
Control is by DALI or by an internal address module, and a version without an interface is also listed. Exit signs use a suspended panel so the legend reads from both sides, with a recognition range of d ≥ 30 m. Single-sided and double-sided variants are offered for escape routes downstairs, to the left and to the right. Wiring is loop in / loop out.
The light source is LED at 5000 K with a luminous flux of 490 ... 775 depending on the variant. Supply is 100 ... 240 V AC at 50 – 60 Hz, or 100 ... 250 V DC. Protection class I. The enclosure is thermoset, the cover polycarbonate and the seal silicone. Ingress protection is IP66 / IP67 and impact strength IK08.
Explosion protection is Ex db eb ib op is IIC T4 Gb for gas and Ex tb op is IIIC T100 °C Db for dust, covering Zone 1 | 2 G | Gb / Zone 2 | 3 G | Gc / Zone 21 | 2 D | Db / Zone 22 | 3 D | Dc. IECEx and ATEX certificates are listed, along with IEC 60598 and IEC 62262. Ambient temperature range is -40 to +50 °C.
Two M25 entries take cable of Ø 7 … 17 mm, and the housing carries 3 drilled M25 holes. Terminals accept 6 mm² solid and 4 mm² finely stranded conductors. A fitting weighs 3.57 kg.
Technical specifications
| Lamp | LED |
|---|---|
| Colour temperature | 5000 K |
| Luminous flux | 490 ... 775 |
| Control interface | without; DALI; Internal address module |
| AC operating voltage | 100 ... 240 V |
| DC operating voltage | 100 ... 250 V |
| Frequency range | 50 – 60 Hz |
| Explosion protection (gas) | Ex db eb ib op is IIC T4 Gb |
| Explosion protection (dust) | Ex tb op is IIIC T100 °C Db |
| Zone | Zone 1 | 2 G | Gb / Zone 2 | 3 G | Gc / Zone 21 | 2 D | Db / Zone 22 | 3 D | Dc |
| IP degree of protection | IP66 / IP67 |
| Impact strength | IK08 |
| Class | I |
| Ambient temperature | -40 ... +50 °C |
| Cable entries | 2 x M25 Ø 7 … 17 mm |
| Enclosure / cover / seal material | Thermoset / Polycarbonate / Silicone |
| Terminals, solid / finely stranded | 6 mm² / 4 mm² |
Part numbers
Show all part numbers (8)
287773, 287785, 287793, 287700, 287782, 287790, 287771, 287699
How it compares with similar models
| Parameter | C-LUX Series 6102 Compact LED Light Fittings, Ex db eb ib op is IIC T4 Gb, IP66/IP67 | Series 6148 Portable LED Lamps, Ex ib IIC T4 Gb, 40000 cd | Series 6149 LED Inspection Light, Ex d IIC, Zones 1, 2, 21, 22, 1396 lm | C-LUX 6109 compact emergency LED luminaire, Ex db eb ib op is IIC T4 Gb |
|---|---|---|---|---|
| Lamp | LED | LED | Single-row LED | — |
| Luminous flux | 490 ... 775 | — | 1396 lm | до 775 lm |
| Explosion protection (gas) | Ex db eb ib op is IIC T4 Gb | Ex ib IIC T4 Gb | II 2 G Ex d IIC T4 Gb; II 2 G Ex d IIC T6 Gb | Ex db eb ib op is IIC T4 Gb |
| Explosion protection (dust) | Ex tb op is IIIC T100 °C Db | Ex tb IIIC T75 °C Db | II 2 D Ex tb IIIC T100 °C Db; II 2 D Ex tb IIIC T80 °C Db | Ex tb op is IIIC T100 °C Db |
| Zone | Zone 1 | 2 G | Gb / Zone 2 | 3 G | Gc / Zone 21 | 2 D | Db / Zone 22 | 3 D | Dc | Zone 1 | 2 G | Gb / Zone 2 | 3 G | Gc / Zone 21 | 2 D | Db / Zone 22 | 3 D | Dc | Zone 1 | 2 G | Gb / Zone 2 | 3 G | Gc / Zone 21 | 2 D | Db / Zone 22 | 3 D | Dc | 1 (2 G, Gb); 2 (3 G, Gc); 21 (2 D, Db); 22 (3 D, Dc) |
| Class | I | II (double insulated) | III | I |
Request a price and lead time
C-LUX Series 6102 Compact LED Light Fittings, Ex db eb ib op is IIC T4 Gb, IP66/IP67. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What explosion protection marking does Series 6102 carry?
Ex db eb ib op is IIC T4 Gb for gas and Ex tb op is IIIC T100 °C Db for dust, for zones 1, 2, 21 and 22.
Can the fitting be controlled over DALI?
Yes. Versions with DALI or an internal address module for central battery systems exist, as well as a version without an interface.
What are the ingress protection and supply ratings?
IP66 / IP67 and IK08. Supply is 100 ... 240 V AC or 100 ... 250 V DC.
Similar equipment from other manufacturers