SDC™, PRC® and POC® condenser bushings for transformers, breakers and switchgear, 15–500 kV
A family of capacitance-graded bushings built on three insulation technologies, cast epoxy SDC™, resin-impregnated paper PRC® and oil-impregnated paper POC®. Between them they cover power and generator step-up transformers, oil circuit breakers, switchgear, wall and floor entries, generators and DC duty.
- Technologies
- SDC™ (cast epoxy), PRC® (resin paper), POC® (oil paper)
- SDC™ voltage class
- 15–145 kV
- PRC® voltage class
- 15–138 kV
- POC® voltage class
- 25–500 kV
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Three core technologies make up the range. POC® uses oil-impregnated paper with porcelain insulators above and below the flange and covers transformers from 25 kV to 500 kV and oil circuit breakers from 25 kV to 230 kV. PRC® has a resin-impregnated paper core, oil-filled or oil-free, with porcelain or polymer sheds at 15–69 kV and polymer only at 115–138 kV.
SDC™ goes furthest from oil: a solid cast composite of APG-02 cycloaliphatic epoxy with integral sheds and condenser core, containing no oil, paper or porcelain, and fit for any angle from vertical to horizontal. It serves air-to-oil and oil-to-oil transformer duty at 15–145 kV, GSU units at 15–35 kV, switchgear at 15–69 kV, wall and floor entries at 15–145 kV, hydrogen-cooled generators at 15–30 kV and DC installations.
Every bushing in the family is seismically certified to IEEE 693, and most designs are transformer–breaker interchangeable (TBI). Production takes place in ISO 9001 certified plants to IEEE C57.19.00/01, CSA C88.1, IEC 60137 or DIN 48124, depending on the order. Besides standard builds, form-fit-function replacements are made for ageing bushings on existing plant.
As a sense of scale, SDC™ part 030-012-T-082-00 is rated 0.68 kV, 30 kV BIL and 1200 A, with a 22 in overall length, 6.7 in creepage and a weight of 25 lb. Send us the nameplate data of the bushing to be replaced and we will identify the matching design.
Technical specifications
| Technologies | SDC™ (cast epoxy), PRC® (resin paper), POC® (oil paper) |
|---|---|
| SDC™ voltage class | 15–145 kV |
| PRC® voltage class | 15–138 kV |
| POC® voltage class | 25–500 kV |
| Current rating | up to 21500 A |
| Media | air–oil, oil–oil, air–air, air–H2 |
| Applications | transformers, oil circuit breakers, switchgear, wall/floor, generators, DC |
| Standards | IEEE C57.19.00/01, CSA C88.1, IEC 60137, DIN 48124 |
| Seismic | IEEE 693 |
| Interchangeability | TBI (transformer–breaker) |
| SDC™ insulation | APG-02 cycloaliphatic epoxy |
| Example SDC™ 030-012-T-082-00 | 0.68 kV, 30 kV BIL, 1200 A, 6.7 in creepage |
Request a price and lead time
SDC™, PRC® and POC® condenser bushings for transformers, breakers and switchgear, 15–500 kV. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which bushing suits an oil-free specification?
SDC™ cast epoxy is fully oil-free from 15 to 145 kV, and PRC® is also available oil-free; POC® always contains oil.
Can an existing bushing be replaced without modifying the tank?
Yes, form-fit-function replacement bushings matching the original mounting dimensions are produced alongside standard designs.
Which standards can the bushings be built to?
IEEE C57.19.00/01, CSA C88.1, IEC 60137 or DIN 48124, all with IEEE 693 seismic certification.