International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

SDC™, PRC® and POC® condenser bushings for transformers, breakers and switchgear, 15–500 kV

A family of capacitance-graded bushings built on three insulation technologies, cast epoxy SDC™, resin-impregnated paper PRC® and oil-impregnated paper POC®. Between them they cover power and generator step-up transformers, oil circuit breakers, switchgear, wall and floor entries, generators and DC duty.

Technologies
SDC™ (cast epoxy), PRC® (resin paper), POC® (oil paper)
SDC™ voltage class
15–145 kV
PRC® voltage class
15–138 kV
POC® voltage class
25–500 kV

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Three core technologies make up the range. POC® uses oil-impregnated paper with porcelain insulators above and below the flange and covers transformers from 25 kV to 500 kV and oil circuit breakers from 25 kV to 230 kV. PRC® has a resin-impregnated paper core, oil-filled or oil-free, with porcelain or polymer sheds at 15–69 kV and polymer only at 115–138 kV.

SDC™ goes furthest from oil: a solid cast composite of APG-02 cycloaliphatic epoxy with integral sheds and condenser core, containing no oil, paper or porcelain, and fit for any angle from vertical to horizontal. It serves air-to-oil and oil-to-oil transformer duty at 15–145 kV, GSU units at 15–35 kV, switchgear at 15–69 kV, wall and floor entries at 15–145 kV, hydrogen-cooled generators at 15–30 kV and DC installations.

Every bushing in the family is seismically certified to IEEE 693, and most designs are transformer–breaker interchangeable (TBI). Production takes place in ISO 9001 certified plants to IEEE C57.19.00/01, CSA C88.1, IEC 60137 or DIN 48124, depending on the order. Besides standard builds, form-fit-function replacements are made for ageing bushings on existing plant.

As a sense of scale, SDC™ part 030-012-T-082-00 is rated 0.68 kV, 30 kV BIL and 1200 A, with a 22 in overall length, 6.7 in creepage and a weight of 25 lb. Send us the nameplate data of the bushing to be replaced and we will identify the matching design.

Technical specifications

TechnologiesSDC™ (cast epoxy), PRC® (resin paper), POC® (oil paper)
SDC™ voltage class15–145 kV
PRC® voltage class15–138 kV
POC® voltage class25–500 kV
Current ratingup to 21500 A
Mediaair–oil, oil–oil, air–air, air–H2
Applicationstransformers, oil circuit breakers, switchgear, wall/floor, generators, DC
StandardsIEEE C57.19.00/01, CSA C88.1, IEC 60137, DIN 48124
SeismicIEEE 693
InterchangeabilityTBI (transformer–breaker)
SDC™ insulationAPG-02 cycloaliphatic epoxy
Example SDC™ 030-012-T-082-000.68 kV, 30 kV BIL, 1200 A, 6.7 in creepage

Request a price and lead time

SDC™, PRC® and POC® condenser bushings for transformers, breakers and switchgear, 15–500 kV. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Which bushing suits an oil-free specification?

SDC™ cast epoxy is fully oil-free from 15 to 145 kV, and PRC® is also available oil-free; POC® always contains oil.

Can an existing bushing be replaced without modifying the tank?

Yes, form-fit-function replacement bushings matching the original mounting dimensions are produced alongside standard designs.

Which standards can the bushings be built to?

IEEE C57.19.00/01, CSA C88.1, IEC 60137 or DIN 48124, all with IEEE 693 seismic certification.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides