International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

VACUTAP VM vacuum OLTC for transformers 72.5–300 kV

Medium power VACUTAP VM vacuum on-load tap changer for power transformers of grids and power plants 72.5–300 kV. Through current is up to 650 A in three-phase and up to 1500 A in single-phase design, and a version for gas-insulated transformers is available.

Highest voltage for equipment Um
72.5–300 kV
Rated through current
up to 650 A (3-phase), up to 1500 A (1-phase)
Step voltage
up to 3300 V
Step capacity
3500 / 1625 kVA (1-phase/3-phase)

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Step voltage is up to 3300 V. Step capacity is 3500 kVA for single-phase and 1625 kVA for three-phase design. The number of positions is up to 22 without a pre-selector and up to 35 with a pre-selector. Besides the basic VM, the range includes the VMS and a gas-insulated design for transformers without oil.

Technical specifications

Highest voltage for equipment Um72.5–300 kV
Rated through currentup to 650 A (3-phase), up to 1500 A (1-phase)
Step voltageup to 3300 V
Step capacity3500 / 1625 kVA (1-phase/3-phase)
Number of positionsup to 22 without pre-selector, up to 35 with pre-selector
Designsincluding VMS and gas-insulated

Replacement for

no direct analogue (vacuum OLTCs) exists; the closest are OLTCs of type РНОА-110/1000, РНТА-35/200, РС-4, РС-9

selected by purpose and main parameters, please confirm with our manager

Request a price and lead time

VACUTAP VM vacuum OLTC for transformers 72.5–300 kV. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Customs codes

UKTZED (Ukraine)8535 90 00 00
HS, 6 digits8535 90
CN (EU)8535 90 00
HTSUS (USA)8535 90 80 60
China customs tariff8535 90 00 90

Codes are for reference: the final code is determined at declaration for the specific model.

Questions and answers

What voltage is the VACUTAP VM designed for?

Um 72.5–300 kV, for transformers of grids and power plants.

Is there a version for gas-insulated transformers?

Yes, besides the VM and VMS a gas-insulated design is available.

What are the step capacity and number of positions?

3500 kVA in single-phase and 1625 kVA in three-phase design. Up to 22 positions without a pre-selector and up to 35 with a pre-selector.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides