International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

VACUTAP VBO bolt-on vacuum resistor-type OLTC up to 40 kV

The VACUTAP VBO is a bolt-on vacuum resistor-type OLTC with a direct drive for transformers up to 40 kV. Its connection dimensions are compatible with existing designs, so it is chosen to replace old tap changers.

Highest voltage for equipment
40 kV
Rated through current
400 A (3-phase)
Step voltage
up to 825 V
Step capacity
330 kVA

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The through current is 400 A in the three-phase version, step voltage up to 825 V and step capacity 330 kVA. The number of positions is 17 without a pre-selector and 33 with a pre-selector. The short-time withstand current is 4 kA for 3 s, and the impulse withstand voltage is 200 kV. The tap changer is operated by the ETOS ID direct drive.

Technical specifications

Highest voltage for equipment40 kV
Rated through current400 A (3-phase)
Step voltageup to 825 V
Step capacity330 kVA
Number of positions17 without pre-selector / 33 with pre-selector
Short-time withstand current4 kA, 3 s
Impulse withstand voltage200 kV
Drivedirect, ETOS ID

Replacement for

no direct analog (vacuum OLTC) exists; the closest are OLTC of types РНОА-110/1000, РНТА-35/200, РС-4, РС-9

selected by purpose and main parameters, please confirm with our manager

Request a price and lead time

VACUTAP VBO bolt-on vacuum resistor-type OLTC up to 40 kV. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Customs codes

UKTZED (Ukraine)8535 90 00 00
HS, 6 digits8535 90
CN (EU)8535 90 00
HTSUS (USA)8535 90 80 60
China customs tariff8535 90 00 90

Codes are for reference: the final code is determined at declaration for the specific model.

Questions and answers

Is the VACUTAP VBO suitable for replacing an old OLTC?

Yes, the connection dimensions are compatible with existing designs. The tap changer is rated for transformers up to 40 kV.

What are the current and step capacity of the VBO?

Through current 400 A (3-phase), step voltage up to 825 V, step capacity 330 kVA.

How many positions does the tap changer have?

17 positions without a pre-selector and 33 with a pre-selector.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides