OLR Remote Oil Level Indicator with Capillary up to 16 m
The OLR passes the oil level reading through a capillary to an indicator mounted at operator eye level, even when the measuring point is high on the transformer. Built-in microswitches provide alarm and control signals, and a 4–20 mA output for SCADA is available as an option.
- Model
- OLR
- Type
- Hydro-mechanical capillary liquid level indicator
- Capillary length
- Up to 52 ft (16 m)
- Number of contacts
- 2 or 4
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The indicator is used to monitor the oil level in conservators and main tanks of transformers, including high-mounted conservators where the scale is hard to see from ground level. The capillary allows the indicator to sit in a safe and convenient place away from the measuring point. It suits new transformers and also replaces indicators on units already in service.
The principle is hydro-mechanical: a float in the tank passes changes in level through the capillary system to the indicator pointer. The unit compensates automatically for the change in hydro-mechanical force caused by the height difference between the measuring point and the indicator. The capillary, up to 52 ft (16 m) long, is protected by stainless steel tubing, and an electronic transmitter is available for longer distances.
The standard version has two fully adjustable magnetic arc-quenching switches for alarm and control of auxiliary equipment, and up to four can be fitted. Contact rating is 3 A at 220 VAC/VDC, and dielectric strength is 2000 VAC for one minute. All connections are made inside the indicator housing, so no cables need to run to the conservator. A 4–20 mA output for remote indication and SCADA can be added to indicators already installed, using a retrofit kit.
The die-cast aluminium housing carries a thermosetting powder coat, and the glass is UV-stabilised polycarbonate that does not yellow over time. The housing is vented and protected from the weather to DIN 40050, rated IP54. The tank flange is anodised aluminium, square or round, for mounting at the top, side or bottom of the vessel.
The float arm length and scale are specified by the customer for the tank geometry. For version 48200-L the float dimensions are A=13 mm and B=55 mm, and for 48200-1-L they are 53 mm and 95 mm, with length L from 500 to 2000 mm. Operating temperature runs from -50 to +70 °C, with ambient humidity from 35 to 100 %.
Technical specifications
| Model | OLR |
|---|---|
| Type | Hydro-mechanical capillary liquid level indicator |
| Capillary length | Up to 52 ft (16 m) |
| Number of contacts | 2 or 4 |
| Contact type | Magnetic, with arc quenching |
| Contact rating | 3 A at 220 VAC/VDC |
| Dielectric strength | 2000 VAC for one minute |
| Output signal | 4–20 mA (option) |
| Mounting | Top, side or bottom, square or round flange |
| Flange | Anodised aluminium |
| Case | Die-cast aluminium |
| Enclosure rating | IP54 (DIN 40050) |
| Lens | UV-stabilised polycarbonate |
| Scale | As specified by the customer |
| Operating temperature | -50…+70 °C |
| Humidity | 35–100% |
| Float 48200-L | A=13 mm, B=55 mm, L=500–2000 mm |
| Float 48200-1-L | A=53 mm, B=95 mm, L=500–2000 mm |
Part numbers
Show all part numbers (3)
48200-L, 48200-1-L, 46701-0
Request a price and lead time
OLR Remote Oil Level Indicator with Capillary up to 16 m. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How far can the indicator be placed from the measuring point?
The capillary is ordered up to 16 m long; for greater distances an optional electronic transmitter is used.
Can a 4–20 mA output be added to an installed indicator?
Yes. Units without an output can be upgraded with a retrofit kit that adds the electronic output.
How many alarm contacts does the indicator have?
Two adjustable magnetic switches as standard, up to four in total, rated 3 A at 220 VAC/VDC.