OLI 34725/44712 transformer oil level indicator with lever float, up to 4 contacts, 4–20 mA
The OLI oil level indicator shows the liquid level continuously in transformer tanks, conservators and tap changer compartments. Its slim lever float fits tight spaces, and up to 4 built-in contacts provide alarm and limit control.
- Type
- Magnetic oil level indicator with lever float
- Maximum level change
- 422 mm
- Dial diameter
- 150 mm or 250 mm
- Scale marks
- Min-Max, Min
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The indicator is fitted to the main tank and conservator of a power transformer, to the tap changer compartment and to other tanks where the liquid level is critical. Contact signals feed transformer protection schemes that warn of, or trip on, low or high oil levels. The analogue output passes the level to SCADA for remote monitoring.
A lever float follows the oil level, and the lever movement reaches the pointer through a magnetic coupling, so the dial housing is separated from the oil volume. The maximum level change is 422 mm. Floats are made from expanded nitrile rubber, steel, cork or acrylic plastic, and the float rod is brass or stainless steel. Mounting is by flange, with flanges of several sizes available and a threaded M50 version.
The dial is 5.9 in (150 mm) or 9.8 in (250 mm) across, with standard Min-Max or Min marks. Contacts are SPST or SPDT, up to 4, rated 3 A at 125 V DC and 5 A at 250 V AC. The 4–20 mA output works into loads up to 500 Ω from a 24 V supply, or a potentiometer from 0 to 1500 Ω is available, and the SCADA interface runs from 24–36 V DC. Signal drift is less than 1% across the nominal temperature range.
Contacts are insulated to 2000 V AC for 60 seconds with respect to the housing, and the 4–20 mA port or potentiometer to 500 V AC for 60 seconds. Electromagnetic immunity is tested to EN61000-6-5 for substation environments, interface 4. The housing is die-cast aluminium with powder coat, with stainless steel parts and UV-stabilised polycarbonate glass that does not yellow over time. Protection is IP54, and vibration resistance is 50/60 Hz with 0.004 in displacement.
Electrical connection is made via a terminal box, quick-disconnect connectors or sealed moisture-protected entries. The manufacturer lists 629 order codes for the 34725 and 44712 variants, for example 34725-4_CS-46293 or 44712-2_CS-43860.
Technical specifications
| Type | Magnetic oil level indicator with lever float |
|---|---|
| Maximum level change | 422 mm |
| Dial diameter | 150 mm or 250 mm |
| Scale marks | Min-Max, Min |
| Contacts | up to 4, SPST or SPDT |
| Contact ratings | 3 A / 125 V DC; 5 A / 250 V AC |
| Analogue output | 4–20 mA, load up to 500 Ω at 24 V |
| Potentiometer | 0 to 1500 Ω |
| SCADA interface supply | 24–36 V DC |
| Signal drift | less than 1% |
| Insulation | contacts 2000 V AC, 4–20 mA port 500 V AC, 60 s |
| Immunity | EN61000-6-5, substation category |
| Float | expanded nitrile rubber, steel, cork, acrylic plastic |
| Float rod | brass or stainless steel |
| Mounting | flange, M50 |
| Protection | IP54 |
| Vibration resistance | 50/60 Hz, 0.004 in |
Part numbers
Show all part numbers (6)
34725-1_CS-46505, 34725-2_CS-60102, 34725-4_CS-46293, 34725CS-4-8, 44712-1_CS-60048, 44712-2_CS-43860
Request a price and lead time
OLI 34725/44712 transformer oil level indicator with lever float, up to 4 contacts, 4–20 mA. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Can the oil level be sent to SCADA?
Yes, the indicator has a 4–20 mA analogue output into loads up to 500 Ω, or a potentiometer output from 0 to 1500 Ω.
How many alarm contacts can be fitted?
Up to 4 SPST or SPDT contacts, rated 3 A at 125 V DC and 5 A at 250 V AC.
What is the maximum level change the indicator tracks?
The maximum change in liquid level is 422 mm.