International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

OILTAP G / V oil-type OLTC, 40–362 kV

OILTAP G and V are classic oil-quenching on-load tap changers for power transformers of 40–362 kV. They are used in the existing fleet and when replacing tap changers.

Highest voltage for equipment Um
OILTAP V: 40–123 kV; OILTAP G: 72.5–362 kV
Rated through current
V: 200/400 A (1-phase/3-phase); G: up to 4500/2000 A
Step voltage
V: up to 1500 V; G: up to 5000 V
Step capacity
V: 525 kVA; G: up to 6500/5000 kVA

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

OILTAP V is rated for Um 40–123 kV, through current 200/400 A (1-phase/3-phase), step voltage up to 1500 V and rated step capacity 525 kVA. OILTAP G works at Um 72.5–362 kV, with current up to 4500/2000 A, step voltage up to 5000 V and step capacity up to 6500/5000 kVA. The number of positions is up to 18, and up to 35 for the G with a pre-selector. The arc during switching is extinguished in oil.

Technical specifications

Highest voltage for equipment UmOILTAP V: 40–123 kV; OILTAP G: 72.5–362 kV
Rated through currentV: 200/400 A (1-phase/3-phase); G: up to 4500/2000 A
Step voltageV: up to 1500 V; G: up to 5000 V
Step capacityV: 525 kVA; G: up to 6500/5000 kVA
Number of positionsup to 18 / up to 35 with pre-selector (G)
Arc extinctionin oil

Replacement for

OLTC of types РНОА-110/1000, РНТА-35/200, РС-3, РС-4, РС-9 (oil-type)

selected by purpose and main parameters, please confirm with our manager

Request a price and lead time

OILTAP G / V oil-type OLTC, 40–362 kV. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Customs codes

UKTZED (Ukraine)8535 90 00 00
HS, 6 digits8535 90
CN (EU)8535 90 00
HTSUS (USA)8535 90 80 60
China customs tariff8535 90 00 90

Codes are for reference: the final code is determined at declaration for the specific model.

Questions and answers

Which voltage classes are OILTAP V and G made for?

OILTAP V is rated for Um 40–123 kV, OILTAP G for Um 72.5–362 kV.

What is the through current of the tap changers?

For the V it is 200/400 A for 1-phase/3-phase versions. For the G it is up to 4500/2000 A.

How many positions does the OILTAP G have?

Up to 18 positions, and up to 35 with a pre-selector. Step voltage is up to 5000 V.