LPRD/208/213/216 Large Pressure Relief Device for Transformers and Tap Changers
LPRD relief devices in the 208, 213 and 216 series quickly vent large volumes of gas or insulating liquid from a transformer or tap changer tank when pressure exceeds the set point. After operation the valve reseals itself, and a pin indicator, flag and signal contacts show its state.
- Type
- mechanical pressure relief valve with automatic reseal
- Set pressure
- 4–14 PSI (±1 PSI); 15–20 PSI (±2 PSI)
- Flow capacity
- about 8400 SCFM at 15 PSIG (10 PSI setting)
- Reseal point
- at roughly half the operating pressure
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
LPRD valves are fitted to power transformer tanks, on-load tap changers and other oil-filled equipment, both on new installations and when old devices are replaced. Once tank pressure reaches the set limit, the valve opens sharply, discharges gas or oil with a loud bang, and closes again at roughly half the operating pressure. The valve tolerates full vacuum without damage.
A patented double-gasket design boosts the opening force and shortens the response time, while a secondary scraper gasket improves resealing. The working valve is stainless steel 304, with studs, bushing and fixings also in stainless steel. The flange is cast aluminium and the ring is aluminium with a chromate conversion coating, and the exposed aluminium parts also carry a thermosetting powder finish. The cover is galvanised steel on the 208 and 213, and stainless steel on the 216. Gaskets are fluorosilicone, nitrile or Viton.
Rated set pressures are chosen from two ranges: 4–14 PSI (0.28–0.97 bar) with a tolerance of ±1 PSI, and 15–20 PSI (1.03–1.38 bar) with a tolerance of ±2 PSI, when the rise rate is 2 psi/sec or faster. A slower rise doubles the tolerance, and the valve may vent pressure without tripping the indicator. A valve set to 10 PSI passes about 8400 SCFM at 15 PSIG. Every valve goes through factory pressure testing, and the results are recorded against its serial number.
Operation is signalled by a brass pin indicator and, on request, a flag in different colours. Standard units have up to two contact housings holding up to four Form C contacts. Contacts can be latching or momentary, SPDT or DPDT, high-voltage DC types, or gold-plated for small currents. Ratings are 1/2 A at 125 VDC and 1/4 A at 250 VDC on a non-inductive load, with insulation of 2000 VAC at 50/60 Hz for one minute. The contact housing is IP65, with an AS1000 contact at IP66. Connection is by plug, terminal box or cable, with a PH-13.5 cable gland and wire up to 2.5 mm² (14 AWG).
Mounting is recommended horizontal with the top side up, though vertical mounting on the side of the tank is allowed with the connector facing down. The mounting hole should be at least 5.25 inches (133 mm). A deflector screen with a pipe connection directs hot oil and gas to one side, and for mounting below the oil level a gas bleed system is provided. The finish withstands 200 hours of salt spray to ASTM B 117 without corrosion. Ambient temperature runs from -40 to +80 °C, and oil from -20 to +100 °C.
Technical specifications
| Type | mechanical pressure relief valve with automatic reseal |
|---|---|
| Set pressure | 4–14 PSI (±1 PSI); 15–20 PSI (±2 PSI) |
| Flow capacity | about 8400 SCFM at 15 PSIG (10 PSI setting) |
| Reseal point | at roughly half the operating pressure |
| Contacts | up to 2 housings, up to 4 Form C |
| Contact rating | 1/2 A at 125 VDC; 1/4 A at 250 VDC |
| Dielectric strength | 2000 VAC, 50/60 Hz, 1 min |
| Contact housing protection | IP65; IP66 with AS1000 |
| Cable gland | PH-13.5, wire up to 2.5 mm² (14 AWG) |
| Flange and ring | cast aluminium |
| Cover | galvanised steel (208/213); stainless steel (216) |
| Valve | stainless steel 304 |
| Gaskets | fluorosilicone / nitrile / Viton |
| Recommended tank opening | from 5.25 inches (133 mm) |
| Salt spray | 200 h to ASTM B 117 |
| Ambient temperature | -40 to +80 °C |
| Oil temperature | -20 to +100 °C |
Request a price and lead time
LPRD/208/213/216 Large Pressure Relief Device for Transformers and Tap Changers. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
At what pressure does the valve close after it operates?
At roughly half of the rated operating pressure, after which the valve seals the tank again.
Can the LPRD be mounted on the side wall of the tank?
Yes, vertically on the side with the connector facing down, although horizontal mounting with the top side up is the recommendation. Hydrostatic head is taken into account when choosing the set point.
What differs between the 208/213 and the 216?
The main cover material: galvanised steel in the 208 and 213, and stainless steel in the 216.
Similar equipment from other manufacturers