44612/44622/44617/44618 Direct Mount Transformer Thermometer
The 44612 series of direct-mount mechanical thermometers shows oil or simulated winding temperature on power transformers. Each unit has a resettable maximum pointer, up to two switches for cooling control and alarms, and an optional Pt100 output for SCADA.
- Type
- Direct-mount mechanical thermometer
- Mounting
- Top mount
- Standard dial ranges
- 10 to 120°C, 0 to 130°C, -20 to 120°C, 60 to 150°C
- Indicating accuracy
- ±2°C from 50 to 120°C
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
These thermometers mount on the cover of a power transformer tank or on a tap changer compartment, with the probe pointing upwards and the scale easy to read. They show the oil temperature continuously. For winding temperature, the version with a heating element built into the probe simulates winding heating from load current, so no separate assembly is needed.
The instrument shows the current temperature along with the maximum recorded since it was last reset. Indicating accuracy is ±2°C between 50 and 120°C. Standard dial ranges are 10 to 120°C, 0 to 130°C, -20 to 120°C and 60 to 150°C. The dial stands 117 mm high, the probe is 95 mm deep and 17 mm in diameter, and the unit weighs about 0.5 kg.
The case holds up to two SPST or SPDT switches for cooling control and alarms. Set points run from 10 to 120°C, with switching accuracy of ±3°C between 50 and 120°C and a differential of about 5°C. Contact ratings are 5 A at 250 VAC and 0.3 A at 110 VDC (L/R = 10 ms), and the contacts withstand 2000 VAC to the case for one minute. An optional Pt100 output passes the temperature to SCADA or a remote monitoring system.
The body is die-cast aluminium with a thermosetting powder coat, and the cover is glass-reinforced thermoset plastic. The lens is UV-stabilised polycarbonate. Protection is IP55 and the ambient operating range is -40 to 70°C. Mounting options are G 3/4, G 1, a 50 x 50 mm flange or a G 3/4 female thread, with an M22 x 1.5 cable gland. The unit needs no routine maintenance and contains no fuse.
Technical specifications
| Type | Direct-mount mechanical thermometer |
|---|---|
| Mounting | Top mount |
| Standard dial ranges | 10 to 120°C, 0 to 130°C, -20 to 120°C, 60 to 150°C |
| Indicating accuracy | ±2°C from 50 to 120°C |
| Number of switches | Up to 2, SPST or SPDT |
| Switch rating AC | 5 A at 250 V |
| Switch rating DC | 0.3 A at 110 V DC, L/R = 10 ms |
| Switching accuracy | ±3°C from 50 to 120°C |
| Switch differential | About 5°C |
| Dielectric isolation | 2000 VAC for one minute |
| Output | Pt100 (optional) |
| Tank connection | G 3/4, G 1, 50 x 50 mm flange, G 3/4 female, 7/8-14 UNC |
| Cable gland | M22 x 1.5 |
| Dial height | 117 mm |
| Probe immersion depth | 95 mm |
| Probe diameter | 17 mm |
| Weight | About 0.5 kg |
| Ingress protection | IP55 |
| Ambient temperature | -40 to 70°C |
Part numbers
Show all part numbers (12)
44612-00-110, 44612-01-125, 44612-01-210, 44612-04-125, 44612-10-110, 44612-00-310, 44617-1, 44618-01-210, 44622-00-110, 44622-01-125, 44622-05-110, 44622-06-110
Request a price and lead time
44612/44622/44617/44618 Direct Mount Transformer Thermometer. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Can this thermometer show winding temperature?
Yes. The version with a heating element in the probe simulates winding temperature, while the standard version is used for oil.
How many switches are there and what load can they carry?
Up to two SPST or SPDT switches, rated 5 A at 250 VAC and 0.3 A DC.
How is the temperature sent to SCADA?
Through the optional Pt100 output, which connects to a remote monitoring system.