44612/44622/44617/44618 Direct Mount Transformer Thermometer

The 44612 series of direct-mount mechanical thermometers shows oil or simulated winding temperature on power transformers. Each unit has a resettable maximum pointer, up to two switches for cooling control and alarms, and an optional Pt100 output for SCADA.

Type
Direct-mount mechanical thermometer
Mounting
Top mount
Standard dial ranges
10 to 120°C, 0 to 130°C, -20 to 120°C, 60 to 150°C
Indicating accuracy
±2°C from 50 to 120°C

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

These thermometers mount on the cover of a power transformer tank or on a tap changer compartment, with the probe pointing upwards and the scale easy to read. They show the oil temperature continuously. For winding temperature, the version with a heating element built into the probe simulates winding heating from load current, so no separate assembly is needed.

The instrument shows the current temperature along with the maximum recorded since it was last reset. Indicating accuracy is ±2°C between 50 and 120°C. Standard dial ranges are 10 to 120°C, 0 to 130°C, -20 to 120°C and 60 to 150°C. The dial stands 117 mm high, the probe is 95 mm deep and 17 mm in diameter, and the unit weighs about 0.5 kg.

The case holds up to two SPST or SPDT switches for cooling control and alarms. Set points run from 10 to 120°C, with switching accuracy of ±3°C between 50 and 120°C and a differential of about 5°C. Contact ratings are 5 A at 250 VAC and 0.3 A at 110 VDC (L/R = 10 ms), and the contacts withstand 2000 VAC to the case for one minute. An optional Pt100 output passes the temperature to SCADA or a remote monitoring system.

The body is die-cast aluminium with a thermosetting powder coat, and the cover is glass-reinforced thermoset plastic. The lens is UV-stabilised polycarbonate. Protection is IP55 and the ambient operating range is -40 to 70°C. Mounting options are G 3/4, G 1, a 50 x 50 mm flange or a G 3/4 female thread, with an M22 x 1.5 cable gland. The unit needs no routine maintenance and contains no fuse.

Technical specifications

TypeDirect-mount mechanical thermometer
MountingTop mount
Standard dial ranges10 to 120°C, 0 to 130°C, -20 to 120°C, 60 to 150°C
Indicating accuracy±2°C from 50 to 120°C
Number of switchesUp to 2, SPST or SPDT
Switch rating AC5 A at 250 V
Switch rating DC0.3 A at 110 V DC, L/R = 10 ms
Switching accuracy±3°C from 50 to 120°C
Switch differentialAbout 5°C
Dielectric isolation2000 VAC for one minute
OutputPt100 (optional)
Tank connectionG 3/4, G 1, 50 x 50 mm flange, G 3/4 female, 7/8-14 UNC
Cable glandM22 x 1.5
Dial height117 mm
Probe immersion depth95 mm
Probe diameter17 mm
WeightAbout 0.5 kg
Ingress protectionIP55
Ambient temperature-40 to 70°C

Part numbers

Show all part numbers (12)

44612-00-110, 44612-01-125, 44612-01-210, 44612-04-125, 44612-10-110, 44612-00-310, 44617-1, 44618-01-210, 44622-00-110, 44622-01-125, 44622-05-110, 44622-06-110

Request a price and lead time

44612/44622/44617/44618 Direct Mount Transformer Thermometer. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Can this thermometer show winding temperature?

Yes. The version with a heating element in the probe simulates winding temperature, while the standard version is used for oil.

How many switches are there and what load can they carry?

Up to two SPST or SPDT switches, rated 5 A at 250 VAC and 0.3 A DC.

How is the temperature sent to SCADA?

Through the optional Pt100 output, which connects to a remote monitoring system.