44611/48471 Top-Mounted Bimetal Thermometer for Transformer Oil
The 44611 and 48471 bimetal thermometers mount on the cover of a transformer tank to show oil temperature directly. They have a reset maximum pointer, a stainless steel case and IP54 protection, and most models screw into a pocket.
- Type
- bimetal top-mounted thermometer
- Scale range
- 10–120 °C
- Error
- ±2 °C from 50 to 120 °C
- Connection
- G 1/2″; G 3/4″; G 1″; O-ring Ø22 mm
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The 44611/48471 thermometers display main tank oil temperature wherever the measuring point, a pocket or well, sits on the top of the unit and the scale can be read without extra fittings. Most models screw into a pocket, so the instrument can be replaced without draining oil from the tank. The thermometer has a low profile and a large pointer that can be read from a distance.
The sensing element is bimetal with damping, so the pointer moves smoothly. The standard scale range is 10–120 °C, with an error of ±2 °C between 50 and 120 °C. The maximum pointer records the highest temperature since it was last reset, so an operator sees the peak value between inspections.
The case, flange and dial are stainless steel, and the seal is a nitrile ring. The lens is clear cast polycarbonate with UV stabilisation and resists scratching. All models have a dust-proof vented design that stops moisture collecting under the lens. Protection is IP54 to IEC 529, which corresponds to NEMA 3S. Ambient operating temperature runs from -40 to +70 °C.
The versions differ in tank connection, probe diameter and probe length. The 44611-1 has a G 1/2″ thread, the 44611-2 a G 3/4″ thread and the 44611-3 a G 1″ thread, and all three have a 14 mm probe 110 mm long. The 48471 connects with a Ø22 mm O-ring seal and has a 17 mm probe 100 mm long. The probe is stainless steel as standard. The thermometers are compatible with pockets 44601 and 48469.
Technical specifications
| Type | bimetal top-mounted thermometer |
|---|---|
| Scale range | 10–120 °C |
| Error | ±2 °C from 50 to 120 °C |
| Connection | G 1/2″; G 3/4″; G 1″; O-ring Ø22 mm |
| Probe diameter | 14 mm or 17 mm |
| Probe length | 100 mm or 110 mm |
| Compatible pockets | 44601, 48469 |
| Case and dial | stainless steel |
| Seal | nitrile O-ring |
| Lens | polycarbonate with UV stabilisation |
| Probe | stainless steel |
| Ingress protection | IP54 to IEC 529 (NEMA 3S) |
| Ambient temperature | -40 to +70 °C |
Part numbers
Show all part numbers (8)
44611-1, 44611-2, 44611-3, 44611-3-1, 44611-3-2, 44611-3-3, 48471, 48471-05
Request a price and lead time
44611/48471 Top-Mounted Bimetal Thermometer for Transformer Oil. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which model suits a G 3/4″ thread?
Model 44611-2, with a G 3/4″ thread, a 14 mm probe and a 110 mm probe length.
Can the thermometer be replaced without draining the oil?
Yes. Most models screw into pocket 44601 or 48469, which stays in the tank.
What accuracy can be expected?
An error of ±2 °C in the working range from 50 to 120 °C.