345 Gen3 OTIWTI Oil and Winding Temperature Indicator, up to 6 Contacts
The 345 Gen3 OTIWTI indicator measures the temperature of the upper oil layers (type 34) or simulates winding temperature (type 35) of a power transformer. It offers up to six independent contacts, analogue outputs, RS-485 Modbus, IP66 protection and a C5-High finish.
- Type
- mechanical oil (type 34) or winding (type 35) temperature indicator
- Measuring range
- 0–150 °C
- Indication error
- ±2 % of full scale
- Number of contacts
- 2, 4 or 6 Form C
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The 345 Gen3 OTIWTI indicators are used to monitor oil and winding temperature in power transformers of all classes. Type 34 shows oil temperature and type 35 shows winding temperature. The unit gives a local dial reading while passing values to remote systems at the same time, which suits transformer fleets with digital monitoring. General requirements follow IEC 60076-22-1.
Winding temperature is simulated by a bellows assembly built into the unit. Current from a current transformer flows through a heater, and the indicator adds to the oil temperature a rise proportional to the load. Secondary CT currents of up to 2.65 A and up to 5 A are supported, and an internal version is available for CT currents up to 2.2 A. The capillary is made of copper-nickel alloy and sheathed in stainless steel.
The standard measuring range is 0–150 °C, with an indication error of ±2 % of full scale at T > 0 °C. The indicator has 2, 4 or 6 Form C contacts with galvanically separated circuits, each set individually, with set point accuracy of ±3 % of full scale. The differential is 12 ± 2 °C as standard, and on request can be adjusted from 5 to 25 °C for all contacts. Contact types are standard, high-voltage DC and gold-plated. Terminals take wire from 1.5 to 4 mm².
Remote outputs are a passive Pt100 or active 4–20 mA, two 4–20 mA outputs and 0–5 VDC, plus digital communication over RS-485 MODBUS. Contact insulation withstands 2000 VAC to earth for 60 seconds, and the analogue output 500 VAC. The overvoltage category is III, pollution degree 2 and insulation class 1.
The housing is cast aluminium, finished in RAL7000 or RAL7035, with a UV-stabilised polycarbonate lens. Protection is IP66, and corrosion resistance is C5-High to ISO 12944. Operating temperature is -40 to 70 °C in the standard version and -60 to 70 °C in the polar version, storage is -50 to 80 °C, and humidity is up to 95 % non-condensing. The cover hinges and can be removed, which simplifies wiring. The unit mounts on an anti-vibration stand in stainless steel as standard, on an elastomer seismic support, or on a universal bracket.
Technical specifications
| Type | mechanical oil (type 34) or winding (type 35) temperature indicator |
|---|---|
| Measuring range | 0–150 °C |
| Indication error | ±2 % of full scale |
| Number of contacts | 2, 4 or 6 Form C |
| Set point accuracy | ±3 % of full scale |
| Differential | 12 ± 2 °C; option 5–25 °C |
| Contact types | standard, high-voltage DC, gold-plated |
| Winding simulation | CT ≤ 2.65 A; CT ≤ 5 A; internal CT ≤ 2.2 A |
| Remote outputs | Pt100; 4–20 mA; two 4–20 mA; 0–5 VDC |
| Communication | RS-485 MODBUS |
| Insulation | contacts 2000 VAC, analogue output 500 VAC, 60 s |
| Housing | cast aluminium, RAL7000 / RAL7035 |
| Ingress protection | IP66 |
| Corrosion resistance | C5-High to ISO 12944 |
| Operating temperature | -40 to 70 °C; polar version -60 to 70 °C |
| Storage temperature | -50 to 80 °C |
| Wire cross-section | 1.5–4 mm² |
| Standard | IEC 60076-22-1 |
Request a price and lead time
345 Gen3 OTIWTI Oil and Winding Temperature Indicator, up to 6 Contacts. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How does the indicator determine winding temperature?
A bellows assembly with a heater, fed by current from a current transformer (CT ≤ 2.65 A or ≤ 5 A), adds a rise above oil temperature that depends on load.
Can readings go to a monitoring system?
Yes, through Pt100, 4–20 mA or 0–5 VDC outputs, or the RS-485 MODBUS digital interface.
Does the indicator work in cold climates?
The standard version works down to -40 °C, and the polar version from -60 to 70 °C.