
206 MPRD medium pressure relief device for transformers and tap changers
The 206 MPRD vents excess pressure in oil-filled transformer tanks, tap changer compartments and other oil-filled equipment, and closes again once the pressure falls. Operating pressure is set in three ranges from 2.9 to 11.6 PSI, with up to two signal contacts, and a protective hood can be fitted or left off.
- Purpose
- protection against excess pressure in oil-filled equipment
- Operating pressure ranges
- 2.9–5.7 PSI; 5.8–8.6 PSI; 8.7–11.6 PSI
- Reseating
- at a pressure of at least half the working pressure
- Number of contacts
- up to 2
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
When an internal fault occurs in a transformer tank, gas and oil pressure rise sharply. Once the set limit is reached, the 206 MPRD releases a large volume of gas or insulating liquid quickly, which helps protect the tank from rupture. Typical applications include tanks holding up to 3000 litres of oil, tap changer compartments and other oil-filled apparatus.
When pressure rises quickly above the working setting, the valve operates with a sharp bang, and after the pressure falls it reseats firmly at a pressure of at least half the working value. The mechanical indicator and optional alarm contacts operate at the same time. The double sealing gasket is mechanically clamped, so it cannot be blown out, and it keeps dirt and moisture away from the assembly. A mesh flow opening passes gas and oil but limits the entry of debris. A built-in screw bleeds air from under the flange after installation.
Operating pressure is set in three ranges: 2.9–5.7 PSI, 5.8–8.6 PSI and 8.7–11.6 PSI. Gaskets are nitrile as standard, or Viton as an option. Up to two contacts for signalling and control can be fitted, with or without a stainless steel hood. The hood sits above the valve and directs hot oil and gas away from personnel and transformer components. Each valve is tested and certified before dispatch, and the test records are kept.
The flange, ring and valve are aluminium with a thermoset powder coating, ANSI #70 as standard and C5-High as an option. The fixings and cover are stainless steel, and the spring is ASTM A229 wire with zinc and chromate finish. The contacts sit in cast IP66 enclosures with a PG 13.5 cable entry, taking conductors up to 2.5 mm2 (14 AWG). Contact ratings are 6 A at 120 V AC, 3 A at 240 V AC, 0.55 A at 125 V DC and 0.27 A at 250 V DC on active load, with a dielectric strength of 2500 V DC for 1 minute.
The recommended tank hole is 75 mm. The preferred mounting is horizontal with the top upward, and side mounting is permitted, but the hydrostatic head from side mounting or a conservator must be allowed for when selecting the operating pressure. The cover is 162.9 mm in diameter and 98.9 mm high, or 122.4 mm with the contact. Ambient temperature runs from -40 °C to +80 °C, and oil temperature from -20 °C to +100 °C.
Technical specifications
| Purpose | protection against excess pressure in oil-filled equipment |
|---|---|
| Operating pressure ranges | 2.9–5.7 PSI; 5.8–8.6 PSI; 8.7–11.6 PSI |
| Reseating | at a pressure of at least half the working pressure |
| Number of contacts | up to 2 |
| Contact ratings | 6 A at 120 V AC; 3 A at 240 V AC; 0.55 A at 125 V DC; 0.27 A at 250 V DC |
| Dielectric strength | 2500 V DC, 50/60 Hz, 1 minute |
| Contact enclosure | IP66 |
| Cable entry | PG 13.5, conductor up to 2.5 mm2 (14 AWG) |
| Cover diameter | 162.9 mm |
| Height | 98.9 mm; 122.4 mm with contact |
| Tank hole | 75 mm |
| Gaskets | nitrile (standard); Viton (optional) |
| Flange, ring and valve | aluminium with powder coating |
| Coating | ANSI #70 (standard); C5-High (optional) |
| Cover and fixings | stainless steel |
| Ambient temperature | -40 °C to +80 °C |
| Oil temperature | -20 °C to +100 °C |
Part numbers
Show all part numbers (25)
206-20V-11, 206-25V-09, 206-30N-12, 206-35N-11, 206-35N-12, 206-35V-00, 206-35V-09, 206-40N-02, 206-40V-00, 206-40V-12, 206-45N-09, 206-45V-00, 206-45V-01, 206-50N-11, 206-50N-19, 206-55N-12, 206-60N-00, 206-65N-02, 206-65N-19, 206-65V-11, 206-70N-12, 206-70N-19, 206-70V-19, 206-75N-00, 206-80V-12
Request a price and lead time
206 MPRD medium pressure relief device for transformers and tap changers. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Can the operating pressure be changed on site?
The valve is factory-set, but it can be adjusted on a test bench within the model's range, followed by retesting.
Which tank volume does the 206 series suit?
It is typically used for tanks holding up to 3000 litres of oil, and for tap changer compartments.
Can the valve be mounted on the side of a tank?
Yes, side mounting is permitted, but the hydrostatic head of the oil is taken into account when choosing the operating pressure.
Similar equipment from other manufacturers






