105 capillary thermometer for transformer oil temperature indication
A mechanical capillary thermometer with a Bourdon tube, for remote display of transformer oil temperature or simulated winding temperature. It has a resettable maximum pointer and up to three built-in contacts for alarms and cooling control. It suits locations where the sensor well is hard to inspect.
- Measuring system
- Bourdon tube, capillary
- Standard scales
- 0–120, 0–160, 0–180, 20–180, 0–200, 0–220, 0–250 °C
- Indication accuracy
- ±2% of span
- Dial diameter
- 4.5 inches
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The 105 measures transformer oil temperature, or the simulated winding temperature, and passes signals to cooling control, alarm circuits and other auxiliary equipment. It is fitted where the sensor well is hard to reach and a separate remote display is needed. The unit is also used on dry-type transformers, and special models are made for bearing temperature. Contact operation can be fed into SCADA and transformer protection schemes.
The measuring system is a Bourdon tube gauge, with the sensor connected to the indicator by a capillary in double copper braid or in a steel flexible conduit. The dial is 4.5 inches across with a 120° pointer sweep, and the digits are 6.35 mm and 12.7 mm high. Standard scales are 0–120, 0–160, 0–180, 20–180, 0–200, 0–220 and 0–250 °C, and other ranges are made to order. Indication accuracy is ±2% of span. The maximum pointer is reset by a knob that works through the glass with a magnetic drive, which lowers the risk of moisture entering the case.
The unit has up to three contacts: two adjustable by the user and one fixed at the factory setting. The contacts are instantaneous SPST or SPDT, rated 10 A at 125, 250 and 480 V AC. On DC they carry 1.5 A at 48 V, half an amp at 125 V and a quarter amp at 250 V on a resistive load. Operating accuracy is ±2% of span, repeatability is ±1.250% of span, and dielectric strength is 1500 V AC for one minute. A Quick-test function checks contact operation: the pointer is moved by hand through the set points, and a spring-loaded coupling protects the mechanism.
The 135 mm case is die-cast aluminium with ANSI #70 powder coating, with a C5-High option, and it has a polycarbonate lens stabilised against UV. The housing is vented, and two breathers act as vacuum valves that keep moisture out. The sensor is brass, 12.2 mm in diameter and 98.3 mm long, with a 7/8-14 UNF-2A thread, and the well is brass or stainless steel with a 1/2-14 NPT thread. The operating range runs from -34 to 60 °C, and the weight is about 1.40 kg. The unit mounts vertically on a back plate or panel, directly on the transformer or on an optional anti-vibration base. Electrical connection is through the maker's own connector, a military or ANSI connector, flexible leads, or a permanently attached cable.
Technical specifications
| Measuring system | Bourdon tube, capillary |
|---|---|
| Standard scales | 0–120, 0–160, 0–180, 20–180, 0–200, 0–220, 0–250 °C |
| Indication accuracy | ±2% of span |
| Dial diameter | 4.5 inches |
| Case diameter | 135 mm |
| Pointer sweep | 120° |
| Number of contacts | up to 3 (2 adjustable, 1 fixed) |
| Contact type | instantaneous, SPST or SPDT |
| Contact rating, AC | 10 A at 125, 250, 480 V AC |
| Contact rating, DC | 1.5 A at 48 V, half an amp at 125 V, quarter amp at 250 V (resistive) |
| Operating accuracy | ±2% of span |
| Repeatability | ±1.250% of span |
| Dielectric strength | 1500 V AC, 1 min |
| Sensor | brass, Ø 12.2 mm, length 98.3 mm, 7/8-14 UNF-2A |
| Well | brass or stainless steel, 1/2-14 NPT |
| Capillary protection | double copper braid or steel flexible conduit |
| Operating temperature | -34 to 60 °C |
| Weight | 1.40 kg |
| Mounting | vertical, on back plate or panel |
Part numbers
Show all part numbers (1)
105
Request a price and lead time
105 capillary thermometer for transformer oil temperature indication. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How many contacts can the 105 thermometer have?
Up to three: two adjustable by the user and one fixed at the factory setting. Several contacts can be set to the same temperature.
How can contact operation be checked without heating the sensor?
With the Quick-test function. The pointer is moved by hand through the set points while the switching is observed. A spring-loaded coupling protects the mechanism from damage.
Is the unit suitable for dry-type transformers?
Yes, the thermometer is used on dry-type transformers for temperature indication. Special models are made for bearings.