International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

042 Gear-Driven Oil Level Gauge for Transformer Tanks

The 042 shows oil level continuously in transformer main tanks, conservators and tap changer compartments. A gear-driven float mechanism amplifies the pointer travel, and built-in SPDT switches handle alarm and limit control.

Type
Magnetic oil level gauge with gear-driven float
Mounting
Flange, several sizes
Dial diameter
6 inches
Housing
Cast aluminium

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The 042 gauge is fitted to the main tank and conservator of oil-filled transformers and to tap changer compartments, along with substation and power plant equipment and industrial vessels where the liquid level is critical. Its contacts produce low and high oil level signals for transformer protection circuits.

The float turns the drive magnet through a gear train, and the pointer in the housing follows that magnet through a magnetic coupling. The gearing gives greater pointer travel for the same float travel, so the level can be read from the ground. The magnetic coupling separates the housing from the oil, so the tank stays sealed and the dial housing can be replaced in place without breaking the seal. A rotating lens allows the switch operation to be checked without dismantling the unit.

The dial is 6 inches in diameter, with standard or custom scales, including MAX, MIN and 25°C markings. Float travel is set to suit the tank geometry, and mounting flanges come in several sizes. Models 032, 042 and 045 can carry up to three switches, and versions with a 0-1 mA or 4-20 mA analogue output pass the level to a remote monitoring system.

Switches are SPDT, rated 0.25 A at 250 VDC and 0.50 A at 125 VDC on resistive loads, and 10 A at 120/240 VAC. The housing is cast aluminium with an ANSI #70 C5-High powder coat and an aluminium flange, while the mechanism parts are stainless steel and other corrosion-resistant materials. The lens is glass, tempered glass or UV-stabilised polycarbonate. Protection is IP65, with a vented version with terminal box at IP55 and a low-temperature (polar) version at IP65. The standard ambient range is -40 to 82°C. Electrical connection is by quick-disconnect fittings, ANSI or military-standard connectors, conduit, or a terminal box.

Technical specifications

TypeMagnetic oil level gauge with gear-driven float
MountingFlange, several sizes
Dial diameter6 inches
HousingCast aluminium
FlangeAluminium
FinishANSI #70 powder coat, C5-High
LensGlass, tempered glass, UV-stabilised polycarbonate
Ingress protectionIP65; vented version IP55
Ambient temperature−40 to 82°C (standard)
Switch typeSPDT
Switch rating DC0.25 A at 250 V, 0.50 A at 125 V, resistive
Switch rating AC10 A at 120/240 V
Analogue output0-1 mA or 4-20 mA (selected models)
Fitted toMain tank, conservator, tap changer compartment

Part numbers

Show all part numbers (12)

042-009-01, 042-021-01, 042-070-01, 042-098-01, 042-60DL, 042-044-01, 042-050-01, 042-099-01, 042-145-02, 042-300-02, 042-304-01, 042-307-01

Request a price and lead time

042 Gear-Driven Oil Level Gauge for Transformer Tanks. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Can the dial be replaced without draining the oil?

Yes. The housing is coupled to the float mechanism by a magnetic coupling, so it can be replaced in place without breaking the tank seal.

How can the switch operation be checked?

By turning the lens, without dismantling the unit. The SPDT contacts switch 10 A at 120/240 VAC.

Can the level be sent to a remote monitoring system?

Yes. Models with a 0-1 mA or 4-20 mA analogue output pass the oil level to a remote system.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides