International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

Compact Oil Level Indicator 035 with SPDT Contacts, 3.75 inch Dial

The 035 indicator shows the oil level in the main tank, conservator or tap changer compartment of a transformer, and its built-in contacts signal low and high levels. The dial case is magnetically coupled to the drive, so it can be removed without breaking the tank seal.

Model
035
Type
Liquid level indicator with magnetic coupling and contacts
Mounting
Flange
Float mechanism
Lever

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The 035 suits power and distribution transformers and related equipment, including small transformers, oil-filled switchgear, industrial transformers, units at renewable energy sites and tap changer compartments. It works as a visual indicator with a dial and pointer, and with contacts fitted it can switch, limit or signal. No external power is needed to operate the indicator.

The drive unit is made of a non-magnetic, non-porous flange, a support tube carrying two bearings, a float, a rod, a drive shaft and a magnet. Oil level changes turn the shaft through the float and rod, while a magnet in the case follows the drive magnet through a magnetic coupling. The contacts are switched by cams on the pointer shaft, and the float mechanism is lever-type.

Up to two independent SPDT contacts can be fitted. Their ratings are 1/2 A at 125 VDC and 1/4 A at 250 VDC on a resistive load, and 10 A at 125, 250 and 480 VAC. Dielectric strength is 1500 VAC for 60 seconds. Connections are made through a terminal box, sealed weatherproof connectors, quick connectors or flying leads, the last being the standard. Wires to a connector or terminal strip must be rated for at least 80 °C.

The die-cast aluminium case carries a thermosetting powder coat to ANSI #70, with C5-High available as an option. The flange is aluminium, the support tube and rod are brass, and the float is brass, cork, Nitrophyl or stainless steel. The lens is glass or UV-stabilised polycarbonate. The depth in the tank is 3 inches (76 mm) and the dial is 3.75 inches, with standard or custom scales.

During installation the case is detached from the drive unit, the rod length is checked, and it is shortened if needed, allowing for 5 mm on the shaft thickness. The drive unit is fixed to the tank with four studs or bolts through a gasket marked top upwards, and the case is then secured with four screws at a torque of no more than 8 in/lbs. Distances from the mounting point to the tank bottom, the high and low alarm levels and the float position are specified on order.

Technical specifications

Model035
TypeLiquid level indicator with magnetic coupling and contacts
MountingFlange
Float mechanismLever
Dial diameter3.75 inches
Depth in tank3 inches (76 mm)
Contact typeSPDT, up to two independent
Contact rating1/2 A at 125 VDC, 1/4 A at 250 VDC (resistive); 10 A at 125, 250 and 480 VAC
Dielectric strength1500 VAC for 60 seconds
ConnectionTerminal box, sealed connectors, quick connectors, flying leads (standard)
CaseDie-cast aluminium
FinishPowder coat ANSI #70 (standard), C5-High (option)
FlangeAluminium
Support tube and rodBrass
FloatBrass, cork, Nitrophyl or stainless steel
LensGlass or UV-stabilised polycarbonate

Part numbers

Show all part numbers (11)

035-020-01, 035-045-01, 035-054-01, 035-020-01_CS-30130, 035-021-01_CS-40631, 035-034-01_CS-33861, 035-039-01_CS-47220, 035-045-01_CS-51719, 035-046-01-S_CS-50883, 035-054-01_CS-62280, 035-300-01_CS-48136

Request a price and lead time

Compact Oil Level Indicator 035 with SPDT Contacts, 3.75 inch Dial. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

How many alarm contacts can be fitted?

Up to two independent SPDT contacts, set for low and high levels or other limiting functions.

Can the case be replaced without draining the oil?

The dial case is magnetically coupled to the drive unit, so it can be removed without breaking the tank seal.

What load can the contacts carry?

10 A at 125, 250 and 480 VAC, and for DC 1/2 A at 125 VDC and 1/4 A at 250 VDC on a resistive load.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides