032 / LLG032 Oil Level Indicator with Lever-Driven Float, 6 inch Dial
This mechanical gauge is fitted to the side wall of a transformer tank, conservator or tap changer compartment. A lever-driven float turns the pointer through a magnetic coupling, and up to three built-in SPDT switches signal limit levels.
- Type
- mechanical liquid level indicator with magnetic coupling
- Float mechanism
- lever
- Mounting
- flange, on the side wall of the tank
- Dial diameter
- 6 inch
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The 032 (LLG032) gauge shows the level of a liquid, normally transformer oil, and mounts directly onto the side wall of a tank. It is fitted to the main tanks and conservators of power and distribution transformers, to load tap changer compartments, to oil-filled switchgear and to industrial transformer installations. The float rides on a radial lever arm that turns the instrument shaft, and the pointer on the 6 inch dial moves between the MAX and MIN marks.
The gauge needs no external power because it is purely mechanical. Movement of the float reaches the pointer through a magnetic coupling, so the dial assembly stays separate from the oil and there is no leakage path. The case carrying the dial can be swapped in situ without lowering the oil level or breaking the tank seal. The lever mechanism has a slimmer profile than a gear drive, which helps where space around the transformer is tight.
The case and bezel are die-cast aluminium, the flange is aluminium, and the finish is ANSI #70 powder coat rated C5-High. The lens is either mineral glass or polycarbonate stabilised against UV light. The support tube is brass, the float rod is brass, copper-plated steel or stainless steel, and the float is made of Nitrophyl. The unit carries an IP65 rating, its standard operating range is -40 to 82 °C, and it tolerates vibration at 50/60 Hz and multiples up to 4x at 0.004 inch displacement.
Up to three SPDT switches can be fitted for alarm signalling, and their set points are chosen by level when the unit is ordered. Contacts are rated 10 A at 120/240 V AC, 0.5 A at 125 V DC or 0.25 A at 250 V DC on non-inductive loads, and they withstand 2000 V AC for 60 seconds. For small currents there is a gold-plated contact option rated 0.10 A at 125 V AC. For continuous remote monitoring an analogue output of 0 to 1 mA or 4 to 20 mA is available.
The model is fully configurable. You can select the flange type and mounting arrangement, the dial legend (MAXMIN25, MAXMIN20, HILO25, ALBA25 or custom text), the pointer travel and its colour, and choose between an outdoor ventilated version (IP55), a sealed version (IP65) or a low-temperature polar version (IP65). Electrical connection can be made with quick-connect plugs, military-type or ANSI connectors, conduit entry or a terminal box. The case, flange assembly or float rod can also be supplied separately.
Technical specifications
| Type | mechanical liquid level indicator with magnetic coupling |
|---|---|
| Float mechanism | lever |
| Mounting | flange, on the side wall of the tank |
| Dial diameter | 6 inch |
| Case and bezel | die-cast aluminium |
| Flange | aluminium |
| Finish | ANSI #70 powder coat, C5-High |
| Lens | mineral glass or UV-stabilised polycarbonate |
| Support tube | brass |
| Float rod | brass, copper-plated steel or stainless steel |
| Float | Nitrophyl |
| Ingress protection | IP65 |
| Operating temperature | -40 to 82 °C (standard) |
| Vibration resistance | 50/60 Hz and multiples up to 4x, 0.004 inch |
| Contacts | up to 3, SPDT |
| Contact rating | 10 A at 120/240 V AC; 0.5 A at 125 V DC; 0.25 A at 250 V DC |
| Contact insulation | 2000 V AC, 60 s |
| Analogue output | 0 to 1 mA or 4 to 20 mA (optional) |
Part numbers
Show all part numbers (8)
032-058-01_CS-43988, LLGZ032-140-01, 032-003-01_CS-30176, 032-60-19A, LLGZ032-305-01, 032-300-02_G1474, LLGZ032-60AB, LLGZ032-35E
Request a price and lead time
032 / LLG032 Oil Level Indicator with Lever-Driven Float, 6 inch Dial. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Can the dial be replaced without draining the oil?
Yes. The dial case is changed on site without lowering the oil level or breaking the tank seal, because the pointer is linked to the float through a magnetic coupling.
How many alarm contacts can be fitted?
Up to three SPDT contacts, rated 10 A at 120/240 V AC. Set points are chosen by level when the unit is ordered.
How does the lever drive differ from a gear drive?
The lever mechanism has a slimmer profile and suits tight spaces, while a gear drive gives a longer pointer travel relative to float travel.