Vertical Oil Level Indicator 029 with Weld-On Flange, 76.2 mm Dial
The 029 vertical indicator uses a gear mechanism to show the oil level in a transformer tank, conservator or tap changer compartment. Its weld-on flange has no gasket, and the stainless steel exterior is rated for prolonged submersion, including in underground installations.
- Model
- 029 (Subway)
- Type
- Vertical liquid level indicator, no contacts
- Mounting
- Weld-on flange without gasket
- Float mechanism
- Geared
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
This indicator is intended for installations where a transformer may stand under water for long periods, such as underground substations and metro networks. It shows the oil level continuously in the main tank, the conservator or a tap changer compartment. Operating staff use it as part of the transformer protection arrangement to check the level, and this version has no signalling contacts, so the reading is local only.
Each unit is calibrated at the factory to within 5° of the scale mark. A float on the rod follows the oil level, and a gear mechanism amplifies the pointer movement relative to the float travel. The larger pointer swing gives finer readings of small level changes than direct linkage would, and no external power is needed because the device is purely mechanical.
The flange is welded onto the tank wall, with no gasket between flange and tank, which removes a leak path through a seal that could age. The flange, bezel and fixings are stainless steel. The case, in brass or stainless steel, carries a thermosetting powder coat in light grey to ASA #70.
The dial diameter is 3.00 inches (76.2 mm) and the flange diameter is 5.00 inches (127 mm). The float rod is brass or copper coated steel, and the float is made from Nitrophyl.
Ordering involves dozens of codes that differ by case material, rod length and scale, and some are built to a custom specification with a CS suffix. To choose a unit, state the case material, rod length, level travel, scale and the flange position on the tank. The flange is welded on when the tank is made or repaired, and the indicator is then fitted to it.
Technical specifications
| Model | 029 (Subway) |
|---|---|
| Type | Vertical liquid level indicator, no contacts |
| Mounting | Weld-on flange without gasket |
| Float mechanism | Geared |
| Flange diameter | 5.00 inches (127 mm) |
| Dial diameter | 3.00 inches (76.2 mm) |
| Calibration | Within 5° of the scale mark |
| Case | Brass or stainless steel, ASA #70 powder coat |
| Bezel | Stainless steel |
| Flange | Stainless steel |
| Float rod | Brass or copper coated steel |
| Float | Nitrophyl |
Part numbers
Show all part numbers (15)
029-001-01, 029-005-01, 029-006-01, 029-009-03, 029-009-08, 029-009-10, 029-009-13, 029-009-14, 029-009-18, 029-009-27, 029-009-35, 029-009-40, 029-010-02, 029-100-01, 029-009-23_CS-61762
Request a price and lead time
Vertical Oil Level Indicator 029 with Weld-On Flange, 76.2 mm Dial. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Can the 029 indicator be fitted to a transformer in an underground chamber?
Yes. The weld-on flange has no gasket, and the stainless steel external parts are rated for long periods under water.
How accurate are the readings?
Each unit is calibrated at the factory to within 5° of the scale mark, and the gear mechanism amplifies the pointer movement.
How is the indicator mounted?
The 127 mm flange is welded to the tank, and the indicator assembly is then fitted onto it.