The 015 mechanical oil level indicator is mounted vertically on the cover of a transformer or conservator tank. Its magnetic coupling removes the leak path through a shaft seal, and an adjustable SPDT contact sends a low-level signal. A gas sampling valve, VLV-609-1, is available as an option.

Mounting
vertical only, from the top
Tank connection
external ISO 228/1-G1.5A thread
Indication error
±6 mm of float travel
Contact
SPDT, adjustable

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The 015 shows the oil level, or the level of another liquid, in real time and switches a contact for alarm or control. It is installed where the measuring point sits at the top of the equipment and the dial is easy to inspect, such as the main tank of a transformer, a conservator or auxiliary tanks. The indicator works both as a visual device and as an electrical level sensor in transformer protection circuits.

The drive is magnetic. A float made of Nitrophyl on a vertical stem passes its movement to the pointer through a magnetic coupling, so there is no traditional shaft seal and no leak path that goes with one. Indication error is ±6 mm of float travel. The dial is colour-coded, with a green band for normal level, a yellow band for low level and a red band for alarm.

The SPDT contact is adjusted on site with a lever on the front of the unit. The standard contact is rated 3 A at 250 V AC and 5 A at 125 V AC, and it carries UL registration and CSA approval. A gold-plated contact rated 0.1 A at 125 V is available as an option for non-inductive loads. Switching error is ±10 mm. Contact insulation withstands 3200 V AC for 60 seconds, the unit is Class II insulated, and no earthing is required.

The housing is aluminium with a chromate and epoxy-polyester coating, and the cover is moulded PBT with a UV-stabilised polycarbonate lens that does not yellow. The vented enclosure is rated IP55 (NEMA 3R) for outdoor installation. It withstands 1000 hours of salt spray to ASTM B:117. Oil temperature can reach 120 °C, and ambient temperature runs from -25 °C to 85 °C.

The tank connection is an external ISO 228/1-G1.5A thread, with an M20 cable gland for cable 8–11 mm across and conductors up to 2.5 mm2. The unit is tightened with a 60 mm spanner through a nut with a gasket, and the body is turned to the required viewing position after installation. The alarm setting is made by lifting the float to a level between 151 and 225 mm, and the normal oil level must be at least 60 mm above the alarm level. The VLV-609-1 valve, together with the KIT-008-1 set, allows gas to be drawn for dissolved gas analysis.

Technical specifications

Mountingvertical only, from the top
Tank connectionexternal ISO 228/1-G1.5A thread
Indication error±6 mm of float travel
ContactSPDT, adjustable
Contact rating3 A at 250 V AC; 5 A at 125 V AC
Optional gold-plated contact0.1 A at 125 V, non-inductive load
Switching error±10 mm
Dielectric strength3200 V AC, 60 s
Housingaluminium, chromate and epoxy-polyester coating
Cover and lensmoulded PBT; UV-stabilised polycarbonate
Float materialNitrophyl
Oil temperatureup to 120 °C
Ambient temperature-25 °C ... 85 °C
ProtectionIP55 (NEMA 3R), vented
Salt spray1000 hours, ASTM B:117
Cable entryM20, cable 8–11 mm, conductor up to 2.5 mm2
Optionsgas sampling valve VLV-609-1

Part numbers

Show all part numbers (20)

015-001-01, 015-001-01_CS-55010, 015-001-01_CS-52325, 015-002-01, 015-002-01_CS-49396, 015-002-01_CS-46399, 015-002-01_CS-49288, 015-002-01_CS-45940, 015-002-01_CS-62790, 015-002-01_CS-43041, 015-002-01_CS-44823, 015-002-01_CS-54882, 015-002-01_CS-54905, 015-002-01_CS-62721, 015-002-01_CS-41845, 015-002-01_CS-55518, 015-002-01_CS-54697, 015-002-01_CS-59661, 015-002-01_CS-43392, 015-002-01_CS-45821

Request a price and lead time

015 vertical oil level indicator with SPDT contact, G1.5A thread, IP55. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

How is the alarm level set?

The float is lifted to the required level between 151 and 225 mm, and the normal oil level must be at least 60 mm above the set point.

What load can the contact carry?

The standard SPDT contact is rated 3 A at 250 V AC or 5 A at 125 V AC, and the optional gold-plated contact is rated 0.1 A at 125 V.

Can gas be sampled through the indicator?

Yes, with the optional VLV-609-1 valve, and the sample is taken with the KIT-008-1 set for dissolved gas analysis.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides