015 vertical oil level indicator with SPDT contact, G1.5A thread, IP55
The 015 mechanical oil level indicator is mounted vertically on the cover of a transformer or conservator tank. Its magnetic coupling removes the leak path through a shaft seal, and an adjustable SPDT contact sends a low-level signal. A gas sampling valve, VLV-609-1, is available as an option.
- Mounting
- vertical only, from the top
- Tank connection
- external ISO 228/1-G1.5A thread
- Indication error
- ±6 mm of float travel
- Contact
- SPDT, adjustable
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The 015 shows the oil level, or the level of another liquid, in real time and switches a contact for alarm or control. It is installed where the measuring point sits at the top of the equipment and the dial is easy to inspect, such as the main tank of a transformer, a conservator or auxiliary tanks. The indicator works both as a visual device and as an electrical level sensor in transformer protection circuits.
The drive is magnetic. A float made of Nitrophyl on a vertical stem passes its movement to the pointer through a magnetic coupling, so there is no traditional shaft seal and no leak path that goes with one. Indication error is ±6 mm of float travel. The dial is colour-coded, with a green band for normal level, a yellow band for low level and a red band for alarm.
The SPDT contact is adjusted on site with a lever on the front of the unit. The standard contact is rated 3 A at 250 V AC and 5 A at 125 V AC, and it carries UL registration and CSA approval. A gold-plated contact rated 0.1 A at 125 V is available as an option for non-inductive loads. Switching error is ±10 mm. Contact insulation withstands 3200 V AC for 60 seconds, the unit is Class II insulated, and no earthing is required.
The housing is aluminium with a chromate and epoxy-polyester coating, and the cover is moulded PBT with a UV-stabilised polycarbonate lens that does not yellow. The vented enclosure is rated IP55 (NEMA 3R) for outdoor installation. It withstands 1000 hours of salt spray to ASTM B:117. Oil temperature can reach 120 °C, and ambient temperature runs from -25 °C to 85 °C.
The tank connection is an external ISO 228/1-G1.5A thread, with an M20 cable gland for cable 8–11 mm across and conductors up to 2.5 mm2. The unit is tightened with a 60 mm spanner through a nut with a gasket, and the body is turned to the required viewing position after installation. The alarm setting is made by lifting the float to a level between 151 and 225 mm, and the normal oil level must be at least 60 mm above the alarm level. The VLV-609-1 valve, together with the KIT-008-1 set, allows gas to be drawn for dissolved gas analysis.
Technical specifications
| Mounting | vertical only, from the top |
|---|---|
| Tank connection | external ISO 228/1-G1.5A thread |
| Indication error | ±6 mm of float travel |
| Contact | SPDT, adjustable |
| Contact rating | 3 A at 250 V AC; 5 A at 125 V AC |
| Optional gold-plated contact | 0.1 A at 125 V, non-inductive load |
| Switching error | ±10 mm |
| Dielectric strength | 3200 V AC, 60 s |
| Housing | aluminium, chromate and epoxy-polyester coating |
| Cover and lens | moulded PBT; UV-stabilised polycarbonate |
| Float material | Nitrophyl |
| Oil temperature | up to 120 °C |
| Ambient temperature | -25 °C ... 85 °C |
| Protection | IP55 (NEMA 3R), vented |
| Salt spray | 1000 hours, ASTM B:117 |
| Cable entry | M20, cable 8–11 mm, conductor up to 2.5 mm2 |
| Options | gas sampling valve VLV-609-1 |
Part numbers
Show all part numbers (20)
015-001-01, 015-001-01_CS-55010, 015-001-01_CS-52325, 015-002-01, 015-002-01_CS-49396, 015-002-01_CS-46399, 015-002-01_CS-49288, 015-002-01_CS-45940, 015-002-01_CS-62790, 015-002-01_CS-43041, 015-002-01_CS-44823, 015-002-01_CS-54882, 015-002-01_CS-54905, 015-002-01_CS-62721, 015-002-01_CS-41845, 015-002-01_CS-55518, 015-002-01_CS-54697, 015-002-01_CS-59661, 015-002-01_CS-43392, 015-002-01_CS-45821
Request a price and lead time
015 vertical oil level indicator with SPDT contact, G1.5A thread, IP55. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How is the alarm level set?
The float is lifted to the required level between 151 and 225 mm, and the normal oil level must be at least 60 mm above the set point.
What load can the contact carry?
The standard SPDT contact is rated 3 A at 250 V AC or 5 A at 125 V AC, and the optional gold-plated contact is rated 0.1 A at 125 V.
Can gas be sampled through the indicator?
Yes, with the optional VLV-609-1 valve, and the sample is taken with the KIT-008-1 set for dissolved gas analysis.