Vacuum-impregnated resin dry distribution transformer, 25 kVA to 5 MVA
Dry resin distribution transformer made with vacuum technology. Rated power is 25 kVA to 5 MVA at up to 36 kV, with aluminium or copper windings and insulation class F or H.
- Rated power
- 25 kVA to 5 MVA
- Rated voltage
- up to 36 kV
- Vector groups
- Dyn5, Dyn11, Yyn0, Ynz5, others on request
- Cooling
- AN, AF
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Distribution transformer, dry type, with vacuum-impregnated resin windings, for the step from a medium-voltage network to low voltage. The network voltage is mostly 15 kV, with 6 kV, 10 kV and 21 kV in smaller areas, and the output is 0.4 kV or another level below 1 kV. It feeds end loads such as industrial plant, municipal consumers and individual customers.
Industrial sites that own medium-voltage lines, or sit next to one, can install these units themselves and branch extra supply points into the plant low-voltage network. Most industrial low-voltage networks run at 0.4 kV, though some end networks are higher, for example 0.66 kV.
The core is cold-rolled transformer steel with inorganic insulation. Windings are aluminium or copper. Insulation class is F or H and cooling is AN or AF. PT100 or PTC probes with protection monitor temperature. The standard enclosure rating is IP00; on request the unit is supplied in a metal enclosure with a stated IP degree, for example IP20, IP21, IP23, IP31, IP33 or IP54.
Standard equipment: thermal protection, PT100 sensors, HV terminals on the coils (M12), flat busbar LV terminals, rating plate, wheeled undercarriage, lifting lugs and earthing terminals on the undercarriage. Optional extras are anti-vibration pads, surge arresters, an enclosure and fans.
Operating limits are altitude up to 1000 m above sea level, ambient temperature -25 to 40 °C and frequency of 50 Hz or 60 Hz. Losses are reduced in line with Commission Regulation (EU) No 548/2014, stages I and II. Manufacture and testing follow PN-EN 60076-1, PN-EN 60076-11 and EN 50588-1. Units with other parameters are agreed individually.
Technical specifications
| Rated power | 25 kVA to 5 MVA |
|---|---|
| Rated voltage | up to 36 kV |
| Vector groups | Dyn5, Dyn11, Yyn0, Ynz5, others on request |
| Cooling | AN, AF |
| Insulation class | F or H |
| Rated frequency | 50 Hz or 60 Hz |
| Core | cold-rolled transformer steel with inorganic insulation |
| Windings | aluminium or copper |
| Sensors | PT100 or PTC probes with protection |
| Enclosure | IP00 as standard, metal enclosure with specified IP on request (IP20, IP21, IP23, IP31, IP33, IP54 etc.) |
| Altitude | up to 1000 m above sea level |
| Ambient temperature | -25 to 40 °C |
| Standards | PN-EN 60076-1, PN-EN 60076-11, EN 50588-1 |
How it compares with similar models
| Parameter | Vacuum-impregnated resin dry distribution transformer, 25 kVA to 5 MVA | TTZG resin mining transformer, 25 kVA to 3 MVA, up to 12 kV | Cast-resin dry-type transformer up to 36 kV, 25–25000 kVA | Cast resin dry-type transformer 6–30 kV, 50 kVA–20 MVA |
|---|---|---|---|---|
| Rated voltage | up to 36 kV | Up to 12 kV | up to 36 kV (series 6.3; 10.5; 15.8; 33 kV) | 6–30 kV |
| Cooling | AN, AF | AN | AN or AF (up to +40 % power with fans) | — |
Request a price and lead time
Vacuum-impregnated resin dry distribution transformer, 25 kVA to 5 MVA. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What power and voltage range is covered?
From 25 kVA to 5 MVA at rated voltage up to 36 kV. Vector groups are Dyn5, Dyn11, Yyn0 and Ynz5, others on request.
Can the transformer be supplied in an enclosure?
Yes. The standard is IP00, and a metal enclosure with a stated IP degree such as IP20, IP21, IP23, IP31, IP33 or IP54 is available on request.
Which loss requirements apply?
Losses are reduced under Commission Regulation (EU) No 548/2014, stages I and II, with manufacture to PN-EN 60076-11 and EN 50588-1.