Dry resin mining transformer for flameproof enclosures, 25 kVA to 3 MVA, up to 12 kV
Three-phase dry resin transformer for massive flameproof enclosures on mining machines. Rated 25 kVA to 3 MVA at up to 12 kV, insulation class H, AN cooling.
- Type
- three-phase dry resin (roving technology) mining transformer
- Rated power
- 25 kVA to 3 MVA
- Rated voltage
- up to 12 kV
- Insulation class
- H (180 °C)
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Mining transformer for use inside massive flameproof enclosures, which are often mounted on large mining machines. Such enclosures have to meet the mining requirements for flameproofing and have very tight dimensions, so the transformers are low-profile and built for harsh working conditions.
The units are three-phase with natural AN cooling and copper windings. The insulation systems use flame-retardant, self-extinguishing materials in insulation class H (180 °C), and at high temperature these materials give off no toxic gases.
The preferred manufacturing method is dry resin with roving technology. HV windings carry epoxy resin insulation. The core is cold-rolled transformer steel with inorganic insulation.
Voltage is adjusted off-circuit on the taps of the HV winding coils, usually within ±5%. The taps can be brought out to a board under a removable cover. The ratio adjustment can be changed on request.
Standard equipment: PT100 sensors, HV and LV terminals led out by cable to the side of the transformer, tap leads also taken out by cable to the side, rating plate, lifting lugs and earthing terminals on the chassis.
The range is 25 kVA to 3 MVA at voltages up to 12 kV. Altitude is limited to 1000 m above sea level, ambient temperature is -25 to 40 °C and frequency is 50 Hz or 60 Hz. Manufacture, testing and tolerances follow PN EN 60076-1 and PN EN 60076-11. Units with other parameters are agreed individually.
Technical specifications
| Type | three-phase dry resin (roving technology) mining transformer |
|---|---|
| Rated power | 25 kVA to 3 MVA |
| Rated voltage | up to 12 kV |
| Insulation class | H (180 °C) |
| Cooling | AN |
| Core | cold-rolled transformer steel with inorganic insulation |
| Windings | copper, HV windings with epoxy resin insulation |
| Voltage adjustment | off-circuit, on HV winding taps, usually ±5% |
| Sensors | PT100 |
| Rated frequency | 50 Hz or 60 Hz |
| Altitude | up to 1000 m above sea level |
| Ambient temperature | -25 to 40 °C |
| Standards | PN EN 60076-1, PN EN 60076-11 |
How it compares with similar models
| Parameter | Dry resin mining transformer for flameproof enclosures, 25 kVA to 3 MVA, up to 12 kV | MOLTRA cast-resin dry-type transformer up to 36 kV, 4000 kVA | TTVA Dry Cast-Resin Transformer for PV, 1000 kVA, 15.75/0.8 kV | Large distribution transformers for BESS and special-purpose transformers up to 9 MVA, 11/33 kV, 2–5 windings |
|---|---|---|---|---|
| Rated power | 25 kVA to 3 MVA | up to 4000 kVA | 1000 kVA | — |
| Windings | copper, HV windings with epoxy resin insulation | aluminum, terminals in copper; vacuum casting of epoxy compound | — | copper or aluminium |
Request a price and lead time
Dry resin mining transformer for flameproof enclosures, 25 kVA to 3 MVA, up to 12 kV. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which enclosures is the transformer built for?
For massive flameproof enclosures, often mounted on large mining machines. Any explosion-protection marking has to be confirmed separately.
What insulation class and cooling are used?
Insulation class H (180 °C), natural AN cooling and copper windings with epoxy resin insulation on the HV side.
How is the voltage adjusted?
Off-circuit on the HV winding taps, usually ±5%. The taps can be brought out to a board under a removable cover.