International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

Safe-NET network transformers 300–2500 kVA for underground networks

Safe-NET network transformers rated 300–2500 kVA for underground secondary networks in large cities. They are installed in vaults, including flood-prone ones, and the tank with enhanced internal arc resistance is patented.

Power
300–2500 kVA, 3-phase
Primary voltage
2.4–34.5 kV
Secondary voltage
216Y/125 – 480Y/277 V (up to 4330Y/2500 V)
Insulating liquid
mineral oil or natural ester

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Three-phase transformers with a primary voltage of 2.4–34.5 kV and a secondary voltage from 216Y/125 to 480Y/277 V, with an upper limit of 4330Y/2500 V. The tank withstands more than 11 MJ of arc energy. The insulating liquid is a choice of mineral oil or natural ester. The design complies with the IEEE C57.12.40 standard.

Technical specifications

Power300–2500 kVA, 3-phase
Primary voltage2.4–34.5 kV
Secondary voltage216Y/125 – 480Y/277 V (up to 4330Y/2500 V)
Insulating liquidmineral oil or natural ester
Tankwithstands more than 11 MJ of arc energy
StandardIEEE C57.12.40

Replacement for

No direct analog; no underground network units; closest are ТМГ-…/10 in БКТП (prefabricated substations)

selected by purpose and main parameters, please confirm with our manager

Request a price and lead time

Safe-NET network transformers 300–2500 kVA for underground networks. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Customs codes

UKTZED (Ukraine)8504 21 00 00
8504 22 10 00
8504 22 90 00
HS, 6 digits8504 22
CN (EU)8504 21 00
8504 22 10
8504 22 90
HTSUS (USA)8504 21 00 60
8504 21 00 80
8504 22 00 40
China customs tariff8504 21 00 00
8504 22 00 00

Codes are for reference: the final code is determined at declaration for the specific model.

Questions and answers

Can the transformer be installed in a vault that floods?

Yes, Safe-NET is produced for underground vaults, including flooded ones. The transformer complies with IEEE C57.12.40.

What internal arc energy does the tank withstand?

The patented tank withstands more than 11 MJ of arc energy.

What voltages are available on the primary and secondary sides?

Primary 2.4–34.5 kV, secondary from 216Y/125 to 480Y/277 V, with an upper limit of 4330Y/2500 V.

Similar equipment from other manufacturers