International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

TPC transformer with built-in switch-fuse 100–250 kVA

TPC is an oil-immersed transformer rated 100–250 kVA with a built-in switch-fuse, a primary voltage of 5–35 kV and a secondary of 410 V. It is intended for cable networks. The built-in protection and disconnection prevent external effects in case of internal damage.

Power
100–250 kVA
Primary voltage
5–35 kV, ±2.5 %
Secondary voltage
410 V
Protection
3 MV striker fuses + three-phase switch-disconnector, earth fault protection from 5 A

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The protection scheme consists of 3 MV striker fuses and a three-phase switch-disconnector, and earth fault protection operates from 5 A. The transformer is used in the NAUVATIS, ECOBLOC and PBS compact substations. The primary voltage is regulated by ±2.5 %, and cooling is natural ONAN. The dielectric is selectable, either PCB-free oil or vegetable oil.

Technical specifications

Power100–250 kVA
Primary voltage5–35 kV, ±2.5 %
Secondary voltage410 V
Protection3 MV striker fuses + three-phase switch-disconnector, earth fault protection from 5 A
CoolingONAN
DielectricPCB-free oil or vegetable oil

Replacement for

ТМГ-100/10…ТМГ-250/10 (in packaged substations); with a built-in switch-fuse there is no direct analog

selected by purpose and main parameters, please confirm with our manager

Request a price and lead time

TPC transformer with built-in switch-fuse 100–250 kVA. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Customs codes

UKTZED (Ukraine)8504 21 00 00
HS, 6 digits8504 21
CN (EU)8504 21 00
HTSUS (USA)8504 21 00 40
8504 21 00 60
China customs tariff8504 21 00 00

Codes are for reference: the final code is determined at declaration for the specific model.

Questions and answers

How is the built-in protection of the TPC arranged?

It is 3 MV striker fuses and a three-phase switch-disconnector. Earth fault protection works from 5 A.

In which substations is the TPC transformer used?

In the NAUVATIS, ECOBLOC and PBS compact substations for cable networks.

What are the power and voltage ranges?

Power 100–250 kVA, primary voltage 5–35 kV with regulation of ±2.5 %, secondary 410 V.