International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

COMTRAXX® CP9xx touch control panels, 7", 15.6" and 24" displays, IP54

The COMTRAXX® CP9xx series covers remote alarm indicators and operator panels with 7" (CP907), 15.6" (CP915) and 24" (CP924) touch displays. They support Modbus, PROFINET, SNMP, MQTT, OPC UA and further protocols, and are rated IP54.

Type
Remote alarm indicators and operator panels, touch TFT
Display size
7" (CP907), 15.6" (CP915), 24" (CP924)
Resolution
800 x 480 (7"), 1280 x 720 (15.6"), 1280 x 720 or 1920 x 1080 (24")
Degree of protection
IP54

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Three display sizes cover small alarm points and full control-room screens in the COMTRAXX® CP9xx series of operator control panels and remote alarm indicators. They serve medical and industrial installations. Alarms, measured values and system states appear on a touch-sensitive TFT display with tempered glass, and critical situations are signalled visually and acoustically. Typical systems are medical isolated power systems (IPS), medical gas supply, ventilation and air-conditioning, room lighting, operating theatre lights, special power supply systems (BSV or UPS) and building control. Building plans can be used for graphical status displays.

The panels are fanless and easy to clean and disinfect. The CP907 has a 7" display (800 x 480), the CP915 a 15.6" display (1280 x 720) and the CP924 a 24" display (1280 x 720 or 1920 x 1080). Interfaces are RS-485, Ethernet, USB and a 3.5 mm audio jack. Protocols are Modbus TCP, Modbus RTU, SNMP, MQTT, PROFINET, EtherNet/IP, OPC UA, PROFIBUS DP, KNX, DeviceNet and BACnet.

Resources include 12 digital inputs, 1600 third-party data points, 30 data loggers of 10000 entries each, a 20000-entry history memory, 50 pages and a background image of up to 3 MB.

The CP907 runs on DC 24 V SELV/PELV (below 15 W), the CP915 and CP924 on AC 100…240 V (below 30 W and below 55 W). All are rated IP54. Operating temperature is –10…+55 °C for the CP907 and –10…+50 °C for the CP915 and CP924, and –5…+40 °C for UL. Altitude is up to 2000 m and humidity up to 98 % at 25 °C. Sizes are 226 x 144 x 78 mm (1.1 kg) for the CP907, 505 x 350 x 92 mm (6.1 kg) for the CP915 and 654 x 441 x 100 mm (9.1 kg) for the CP924, or 441 x 654 x 100 mm in portrait.

Mounting is flush or surface. A suction lifter is needed to remove the display for maintenance. Customised panels with a foil front are available for new builds and retrofits. The series follows IEC 60364-7-710, IEC 61557-8, IEC 60664-1 and IEC 61326-1, with CE and UKCA marking.

Technical specifications

TypeRemote alarm indicators and operator panels, touch TFT
Display size7" (CP907), 15.6" (CP915), 24" (CP924)
Resolution800 x 480 (7"), 1280 x 720 (15.6"), 1280 x 720 or 1920 x 1080 (24")
Degree of protectionIP54
Supply voltageCP907 DC 24 V SELV/PELV; CP915 and CP924 AC 100…240 V
Power consumptionCP907 < 15 W; CP915 < 30 W; CP924 < 55 W
Operating temperatureCP907 –10…+55 °C; CP915 and CP924 –10…+50 °C
Operating temperature for UL–5…+40 °C
Altitude≤ 2000 m
Relative humidity≤ 98 % at 25 °C
Digital inputs12
InterfacesRS-485, Ethernet, USB, 3.5 mm audio jack
ProtocolsModbus TCP, Modbus RTU, SNMP, MQTT, PROFINET, EtherNet/IP, OPC UA, PROFIBUS DP, KNX, DeviceNet, BACnet
Third-party data points1600
Data loggers30 x 10000 entries
History memory20000 entries
Pages50
Dimensions226 x 144 x 78 mm (CP907); 505 x 350 x 92 mm (CP915); 654 x 441 x 100 mm (CP924)
Weight1.1 kg (CP907); 6.1 kg (CP915); 9.1 kg (CP924)

Part numbers

Show all part numbers (16)

B95061080, B95061093, B95061081, B95061085, B95061083, B95061084, B95061086, B95061087, B95100140, B95061112, B95061113, B95061115, B95061116, B95061915, B95061910, B95061911

How it compares with similar models

ParameterCOMTRAXX® CP9xx touch control panels, 7", 15.6" and 24" displays, IP54COMTRAXX® CP907-I condition monitor with 7" display and gateway, DC 24 VCOMTRAXX® COM465IP condition monitor with Ethernet gateway, AC/DC 24…240 VCOMTRAXX® CP305 remote alarm indicator with 5" touch display for medical IT systems
TypeRemote alarm indicators and operator panels, touch TFTCondition monitor with display and gatewayCondition monitor with integrated gatewayRemote alarm indicator for medical IT systems
Supply voltageCP907 DC 24 V SELV/PELV; CP915 and CP924 AC 100…240 VDC 24 V SELV/PELV, ±20 %AC/DC 24…240 V, 50…60 HzAC/DC 24 V
Power consumptionCP907 < 15 W; CP915 < 30 W; CP924 < 55 W—≤ 6,5 VA / ≤ 4 W< 4,2 W
Operating temperatureCP907 –10…+55 °C; CP915 and CP924 –10…+50 °C–10…+55 °C (UL –10…+50 °C)—–10…+55 °C
InterfacesRS-485, Ethernet, USB, 3.5 mm audio jackRS-485, Ethernet, USBRS-485, EthernetRS-485, Ethernet (RJ45)
ProtocolsModbus TCP, Modbus RTU, SNMP, MQTT, PROFINET, EtherNet/IP, OPC UA, PROFIBUS DP, KNX, DeviceNet, BACnetModbus RTU, Modbus TCP, PROFINET, OPC UA, MQTT, SNMPModbus TCP, Modbus RTU, SNMP, PROFINET, MQTT, BCOMBMS internal, Modbus RTU, Modbus TCP, TCP/IP, DHCP, SNTP

Request a price and lead time

COMTRAXX® CP9xx touch control panels, 7", 15.6" and 24" displays, IP54. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Which display sizes are available?

7" (CP907, 800 x 480), 15.6" (CP915, 1280 x 720) and 24" (CP924, 1280 x 720 or 1920 x 1080).

How are the panels powered?

The CP907 from DC 24 V SELV/PELV, the CP915 and CP924 from AC 100…240 V. Consumption is below 15 W, 30 W and 55 W respectively.

Which protocols and resources do the panels support?

Modbus, SNMP, MQTT, PROFINET, OPC UA, BACnet and others. There are 12 digital inputs, 1600 third-party data points and 30 data loggers.