Quadri*Sil HL High-Creepage Silicone Suspension Insulators, Alternating Sheds, 25 kip

High-leakage versions of the Quadri*Sil silicone suspension family for transmission lines crossing heavily polluted ground. Large and small sheds alternate along a 25 kip core, with ductile iron end fittings.

Housing material
Silicone rubber, hydrophobic
End fitting material
Ductile iron
Shed profile
Alternating
Shed diameters
4.0 in / 2,8 in

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Compared with the standard-leakage SL range, the HL design packs more creepage into the same section length. Sheds of 4.0 in and 2,8 in diameter alternate along the housing, so a 20-shed unit reaches 64 in (1619 mm) of creepage. That margin is what heavily polluted routes call for.

Take S025021H2010 as the example: 69.00 kV class, 20 sheds, Y-Clevis at the ground end and ANSI Ball at the line end. Critical impulse flashover is 305 and 325 kV, lightning impulse withstand 350 and 370 kV, and 60 Hz flashover 220 kV dry and 210 kV wet, with a wet withstand of 140 kV. Dry arcing distance is 22 in (559 mm); section length is 33.3 in with the ball end and 34.92 in on the Chain Eye version S025021H2000.

Mechanically the range sits in the 25 kip class: a 5/8 in (16 mm) rod, 25000 lb ultimate rating and a routine test load of 12,500 lbs. The housing is hydrophobic silicone rubber over 3 mm thick, and the end fittings are ductile iron.

Ground-end and line-end fittings are chosen from Y-Clevis, Chain Eye, ANSI Ball, ANSI Socket and ANSI Strait Clevis. Shed count and fitting pair are both encoded in the catalogue number, so quote it in full when you send an enquiry.

Technical specifications

Housing materialSilicone rubber, hydrophobic
End fitting materialDuctile iron
Shed profileAlternating
Shed diameters4.0 in / 2,8 in
Mechanical class25 kip, 5/8 in (16 mm) rod
Ultimate strength rating25000 lb
Routine test load12,500 lbs
End fittingsY-Clevis, Chain Eye, ANSI Ball, ANSI Socket, ANSI Strait Clevis
Voltage class (S025021H2010)69.00 kV
Creepage (S025021H2010)64 in (1619 mm)
Dry arcing distance (S025021H2010)22 in (559 mm)
Critical impulse flashover (S025021H2010)305 / 325 kV
60 Hz flashover, dry / wet (S025021H2010)220 / 210 kV

How it compares with similar models

ParameterQuadri*Sil HL High-Creepage Silicone Suspension Insulators, Alternating Sheds, 25 kipQuadri*Sil SL Silicone Suspension Insulators, Standard Creepage, 25 kip RatingQuadri*Sil EHL Extra High Leakage Silicone Suspension Insulator, 25 kip to 160 kNPCN Toughened Glass Disc Insulators for Suspension Strings, 15000 to 50000 lb Classes
Shed profileAlternatingUniformalternating—
Ultimate strength rating25000 lb25000 lb—15000–50000 lb

Request a price and lead time

Quadri*Sil HL High-Creepage Silicone Suspension Insulators, Alternating Sheds, 25 kip. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

How much extra creepage does HL give over SL?

On 20-shed units HL reaches 64 in (1619 mm), more than the uniform-shed SL design.

Where is the HL version normally fitted?

On lines of 69 kV and above where the route runs through heavily polluted ground.

What is the mechanical rating?

25 kip class, meaning 25000 lb ultimate rating and a routine test load of 12,500 lbs.