International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

ROF / RGF / RGK resistive-capacitive voltage dividers 72.5–550 kV

Resistive-capacitive voltage dividers for 72.5–550 kV, i.e. low-power voltage sensors for metering and power quality measurement. Frequency band from DC to 30 kHz, versions for outdoor switchyards and GIS are available.

Rated voltage
72.5–550 kV
Frequency band
DC – 30 kHz
Design
ROF — oil insulation (mineral or vegetable oil); RGF — gas-insulated for outdoor switchyards; RGK — for GIS
Application
metering, power quality, HVDC

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

ROF has oil insulation with mineral or vegetable oil. RGF is gas-insulated for outdoor switchyards, RGK is installed in GIS. The wide frequency band makes harmonics and transients visible, and the DC component makes the dividers suitable for HVDC. The low-level output signal is fed to digital meters and power quality analysers.

Technical specifications

Rated voltage72.5–550 kV
Frequency bandDC – 30 kHz
DesignROF — oil insulation (mineral or vegetable oil); RGF — gas-insulated for outdoor switchyards; RGK — for GIS
Applicationmetering, power quality, HVDC

Replacement for

no direct analogue; the closest are НДЕ capacitor VTs (general type)

selected by purpose and main parameters, please confirm with our manager

Request a price and lead time

ROF / RGF / RGK resistive-capacitive voltage dividers 72.5–550 kV. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Customs codes

UKTZED (Ukraine)8504 31 21 00
HS, 6 digits8504 31
CN (EU)8504 31 21
HTSUS (USA)8504 31 20 00
China customs tariff8504 31 10 00

Codes are for reference: the final code is determined at declaration for the specific model.

Questions and answers

What is the frequency band of the ROF, RGF, RGK dividers?

From DC to 30 kHz, so they are suitable for power quality measurement and HVDC.

Which version should be chosen for GIS?

RGK. For outdoor switchyards there are the gas-insulated RGF and the oil-insulated ROF.

Can a divider with vegetable oil be ordered?

Yes, the ROF is made with mineral or vegetable oil for 72.5–550 kV.