RELV-CT Rectangular Zero Sequence Current Transformer, Resin Encapsulated
The RELV-CT is a low voltage rectangular zero sequence current transformer in a resin encapsulated body. It is slipped over bushings or insulated cable so that three phases and the neutral pass through its window, and it is used to detect phase to earth faults.
- Type
- Zero sequence current transformer, rectangular
- Design
- Slip-on, external mounting
- Housing
- Resin encapsulated, low profile
- Conductors through window
- Three phases and neutral
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
A zero sequence current transformer responds to an imbalance in the currents in the conductors that pass through its window. In normal operation the sum of the three phase currents and the neutral is close to zero, so the secondary signal is minimal. When one phase faults to earth, part of the current returns outside the window, an imbalance appears, and a signal develops in the secondary winding that operates the earth fault protection relay.
The RELV-CT has a rectangular window sized to take all three phases and the neutral conductor. It is a slip-on type: the transformer is mounted externally by fitting it over the bushings of the equipment or over an insulated cable, without dismantling the busbars. The winding and core are encapsulated in resin, and the low body profile means the unit takes up little space in a compartment or cable chamber.
The transformer's own insulation is low voltage, rated 0.6 kV. It can also be used in installations of higher voltage, provided it is placed over a bushing or an insulated cable, which isolate it from the primary voltage. According to the manufacturer the weight is 160 lb, so the mounting arrangement needs a support structure of suitable strength.
The product is intended for detecting imbalance and earth faults, with the signal passed to a relay. The turns ratio, window dimensions and accuracy class are set for each specific installation. Selection requires the dimensions and position of the bushings or cables that must pass through the window, the number of conductors, the type of protection relay and the required operating current.
During installation all phase conductors and the neutral are passed through the window together, and cable screens are earthed with regard to the direction of their passage through the transformer, so that current in the screen does not distort the zero sequence signal.
Technical specifications
| Type | Zero sequence current transformer, rectangular |
|---|---|
| Design | Slip-on, external mounting |
| Housing | Resin encapsulated, low profile |
| Conductors through window | Three phases and neutral |
| Function | Detection of imbalance and phase to earth fault, signal to relay |
| Installation | Over a bushing or insulated cable |
| Insulation class (BIL per manufacturer) | 0.6 kV 10 % |
| Weight | 160 lb |
Request a price and lead time
RELV-CT Rectangular Zero Sequence Current Transformer, Resin Encapsulated. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Can the RELV-CT be used above 0.6 kV?
Yes, provided it is placed over a bushing or an insulated cable, which isolate it from the primary voltage.
Which conductors pass through the window?
All three phases and the neutral together. The secondary signal then appears only when there is an imbalance, including an earth fault on one phase.
What is needed for selection?
The dimensions and position of the bushings or cables, the number of conductors, the type of protection relay and the required operating current.