LRGBJ-ZHD Current Transformer for High Currents, 40.5–252 kV, up to 5000 A
LRGBJ-ZHD current transformers are rated 40.5 to 252 kV with working primary currents up to 5000 A, and up to 8000 A in certain configurations. The design combines two current transformers in one unit.
- Rated voltage
- 40.5–252 kV
- Primary current
- above 2500 up to 5000 A (up to 8000 A in certain conditions)
- Secondary current
- 5 A, 1 A
- Rated output
- 10–50 VA
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The upper stage takes the high-current conductor and has a ratio of K1, while the lower stage is a high-voltage current transformer with a ratio of K2 that receives the secondary current of the upper stage. The overall ratio is K = K1 × K2, so the range of ratios can be chosen flexibly. The unit measures current for metering and feeds protection relays.
The rated primary voltage is 40.5 to 252 kV, and the rated primary current runs from above 2500 A up to 5000 A, or to 8000 A in certain conditions. The secondary current is 5 A or 1 A, the rated output 10 to 50 VA, with 1 to 8 secondary windings. Metering cores come in 0.2S, 0.2, 0.5S and 0.5 classes, protection cores in 5P, 10P and TPY, with an accuracy limit factor of 5, 10, 15, 20, 30 or 40. Partial discharge is below 5 pC. The 252 kV class has insulation levels of 460/1050/1200 kV and the 126 kV class 230/550/630 kV.
The units are supplied as LRGBJ-ZHD-252/6000, -126/6000, -72/6000 and -40.5/6000, with rated currents of 5000 to 6000 A in the model table. Height ranges from 1150 mm for the 40.5 kV class to 2950 mm for the 252 kV class. The ambient temperature range is -50 to +45 °C.
The units conform to IEC-61869-2 and IEEE C57.13, and the protection transformers are built to IEC-44-6 for transient operation. No maintenance is required, although an optional annual tan δ check is offered. The secondary circuit must not be opened while the unit is energised. An enquiry should state the standard, voltage, current, frequency, ratio, number of secondary windings, output, accuracy classes, accuracy limit factor, instrument security factor, altitude and pollution level.
Technical specifications
| Rated voltage | 40.5–252 kV |
|---|---|
| Primary current | above 2500 up to 5000 A (up to 8000 A in certain conditions) |
| Secondary current | 5 A, 1 A |
| Rated output | 10–50 VA |
| Metering accuracy classes | 0.2S, 0.2, 0.5S, 0.5 |
| Protection accuracy classes | 5P, 10P, TPY |
| Accuracy limit factor | 5, 10, 15, 20, 30, 40 |
| Secondary cores | 1–8 |
| Insulation level 252 kV | 460/1050/1200 kV |
| Insulation level 126 kV | 230/550/630 kV |
| Partial discharge | <5 pC |
| Ambient temperature | -50…+45 °C |
| Height (40.5 / 72 / 126 / 252 kV) | 1150 / 1550 / 1900 / 2950 mm |
| Standards | IEC-61869-2, IEEE C57.13, IEC-44-6 |
Part numbers
Show all part numbers (4)
LRGBJ-ZHD-252/6000, LRGBJ-ZHD-126/6000, LRGBJ-ZHD-72/6000, LRGBJ-ZHD-40.5/6000
Request a price and lead time
LRGBJ-ZHD Current Transformer for High Currents, 40.5–252 kV, up to 5000 A. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How is the LRGBJ-ZHD ratio formed?
The upper stage has a ratio of K1 and the lower high-voltage stage has K2, giving an overall ratio K = K1 × K2.
Which data are needed for an enquiry?
The standard, voltage, current, frequency, ratio, number and output of secondary windings, accuracy classes, accuracy limit factor, instrument security factor, altitude and pollution level.
Does the unit need maintenance in service?
No maintenance is required. An annual tan δ check is available as an option, and the secondary circuits must not be opened during operation.