LRGBJ and GDGL Current Transformers with Dry Insulation for Voltages to 600 kV
Current transformers with dry capacitor insulation, rated for 5000 A and 600 kV. The bushing is U-shaped, and no oil, SF6 gas or paper is involved, so the device cannot explode or leak toxic substances.
- Voltage class
- up to 600 kV
- Current rating
- 5000 A, up to 8000 A in special cases
- Metering classes
- 0.2 and 0.2S, then 0.5 and 0.5S
- Protection classes
- 5P, 10P and TPY
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
A current transformer isolates the high-voltage side from the metering and control side through magnetic linkage. It has two jobs: measuring the line current, and detecting abnormal conditions that start relay protection. This is why one unit stands on every bay of a substation, and a failure can knock out part of the grid and cost a great deal.
The primary circuit runs through a U-shaped bushing, and graded dry capacitor layers surround it. No oil, gas or paper is present anywhere in the device. The insulating material is a polymer film, mostly PTFE (polytetrafluoroethylene), which keeps a very low dielectric loss tangent and a low partial discharge level throughout service. With insulation that needs no servicing, the transformer is lighter than oil-filled or SF6 models.
Metering accuracy classes are 0.2 and 0.2S, then 0.5 and 0.5S, and protection classes are 5P, 10P and TPY; other classes are supplied on request. The secondary side can carry up to 10 windings. Rated current is 5000 A, rising to 8000 A in special cases. The line-up includes several families. LRGBJ ZH Cascade stacks two tiers for EHV and UHV grids. The single-core LRGBJ covers voltages up to 250 kV. Very large currents are served by LRGBJ – ZHD, and GDGL is an optical-electronic device for digital substations and Smart Grid projects. Shunt capacitor bank applications have dedicated variants, where accuracy at very small currents is critical.
Environmental and mechanical qualification covers thermal cycling between +40 °C and -50 °C, water spray for 15 minutes under IEC 60060-1, plus an internal arc rated 63 kA lasting 0.3 seconds, and seismic withstand to IEEE 693 at the high level. The designs conform to CAN/CSA, IEEE and IEC requirements, and special configurations are offered for unusual project specifications.
Technical specifications
| Voltage class | up to 600 kV |
|---|---|
| Current rating | 5000 A, up to 8000 A in special cases |
| Metering classes | 0.2 and 0.2S, then 0.5 and 0.5S |
| Protection classes | 5P, 10P and TPY |
| Secondary windings | maximum of 10 |
| Primary insulation | dry, HV DryShield®, PTFE film |
| Bushing | U-shaped |
| Thermal cycling | +40 °C to -50 °C |
| Water spray | 15 min, IEC 60060-1 |
| Internal arc | 63 kA, 0.3 s |
| Seismic | IEEE 693, high level |
| Series | LRGBJ, GDGL, LRGBJ ZH Cascade and LRGBJ – ZHD |
Request a price and lead time
LRGBJ and GDGL Current Transformers with Dry Insulation for Voltages to 600 kV. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Why is dry insulation preferable to oil or SF6?
Dry insulation contains no oil, gas or paper, so an explosion or a toxic leak is not possible. The device needs no insulation servicing and is lighter than older designs.
Which accuracy classes exist?
Metering classes are 0.2 and 0.2S, then 0.5 and 0.5S. Protection classes are 5P, 10P and TPY. Other classes are made to order.
Which series fits a 250 kV network?
LRGBJ ZH Cascade serves EHV and UHV networks, while the single-core LRGBJ covers voltages up to 250 kV.