International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

GDGL optical/electronic current transformer, 40.5 kV to 252 kV, Rogowski coil sensing

Substations moving towards full digital protection and metering need current sensing that can be digitised at source. The GDGL series does this with a Rogowski coil fitted around a conventional HV primary winding, and sends the result to the local control system.

Type
optical/electronic current transformer
Highest equipment voltage
40.5 / 72.5 / 126 / 252 kV
Power-frequency withstand voltage
95 / 140 / 230 / 460 kV
Lightning impulse withstand voltage
185 / 325 / 550 / 1050 kV

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Many optical CTs place their sensing head on the primary line and draw power from it. GDGL takes a different route: it keeps the manufacturer's proven primary winding and insulation system and adds a Rogowski coil around that winding. The electrical insulation therefore behaves just like a classic unit, while the measurement side becomes electronic.

In service this brings three practical options. First, the transformer fits exactly where a conventional CT stood, on the same support, so the substation layout stays as it is. Second, an operator who must replace CTs now but will go digital later can order the LRGBJ-V: it runs as an analogue CT with the sensor already built in, and once the rest of the station has been upgraded the manufacturer's engineers fit the electronics on site and activate the coil. Third, a dual version can supply analogue and digital signals at the same time.

Compared with an iron-core design, the electronic measurement offers high accuracy across a wide dynamic range, wide bandwidth, no saturation, no noise and stable readings. All other characteristics match the standard LRGBJ series.

Insulation levels are set per voltage class. For 40.5, 72.5, 126 and 252 kV the power-frequency withstand values are 95, 140, 230 and 460 kV, and the lightning impulse withstand values are 185, 325, 550 and 1050 kV. Partial discharge is held to 5 pC, and the permitted ambient range is -40 °C to +85 °C.

Technical specifications

Typeoptical/electronic current transformer
Highest equipment voltage40.5 / 72.5 / 126 / 252 kV
Power-frequency withstand voltage95 / 140 / 230 / 460 kV
Lightning impulse withstand voltage185 / 325 / 550 / 1050 kV
Partial discharge level5 pC
Ambient temperature-40 °C to +85 °C
Sensing elementRogowski coil on the primary winding
Outputdigital; dual analogue + digital version possible
Transitional versionLRGBJ-V with built-in sensor

Request a price and lead time

GDGL optical/electronic current transformer, 40.5 kV to 252 kV, Rogowski coil sensing. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Can a GDGL unit replace an existing conventional CT?

Yes, it mounts in the same position on the same support, so no substation re-layout is needed.

Is there a route for a staged move to digital?

Order the LRGBJ-V, which works as an analogue CT with the sensor built in; electronics are added on site after the station upgrade.

What insulation levels apply at 252 kV?

Power-frequency withstand of 460 kV, lightning impulse withstand of 1050 kV and a partial discharge level of 5 pC.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides